ID | Regulation | Diagnosis | Default Severity |
1 | 537.6.3 | A fire-fighter's switch for an exterior installation requires positioning outside of the building adjacent to the equipment or a notice adjacent to the equipment indicating the position of the switch and a notice adjacent to the switch clearly indicating it's purpose. For an interior installation the switch is required to be positioned in the main entrance or in a position agreed with the local fire authority with the switch to be in a conspicuous position reasonably accessible to fire-fighters at no more than 2.75metres from the ground or standing beneath the switch. Where more than one switch is installed each switch is to be clearly marked to indicate the part of the installation it controls. Regulation 537.6.3 (soi7.3.2) | C3 |
2 | 537.6.1 | A fire-fighter's switch is required in the low voltage circuit supplying exterior electrical installations and interior discharge lighting operating at voltages exceeding low voltage (greater than 50V and 600V Uo a.c or greater than 120V and 900V between conductors or earth). Regulation 537.6.1 (soi7.3.1) | C2 |
3 | 537.6.4 | A fire-fighter's switch is required to be coloured red and to have on it or adjacent a durable label marked “FIREFIGHTER'S SWITCH”, the label shall be a minimum size of 150mm by 100mm with it's lettering easily legible from a distance appropriate to the site conditions but not less than 36 point. The “ON” and “OFF” positions require to be clearly indicated with the “OFF” position at the top and designed or provided with a device to stop the switch from being inadvertently switched to it's “ON” position. Regulation 537.6.4 (soi7.3.5) | C3 |
4 | 416.2.2 | A horizontal top surface of any enclosures or barriers containing live parts which is readily accessible shall be provided with at least a degree of protection IPXXD or IP4X. Regulation 416.2.2 (soi5.5) | C1 |
5 | 512 | Accessory(s) require the correct I.P rating for the situation in which they are used. Section 512 (soi6.25) | C2 |
6 | 530.4.1 | Accessory(s) requires mounting in a permanent fashion or re-fixing where it has become loose. Regulation 530.4.1 (soi6.24) | C2 |
7 | 701.411.3.3 | All items of electrical equipment, cable(s) and wiring systems in locations containing a bath or shower require additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn. Regulation 701.411.3.3 (soi9.1, soi9.0) | C3 |
8 | 411.3.3 | All socket(s) that are outside of the equipotential area require additional RCD protection having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn. Regulations 411.3.3 & 415.1.1 (soi5.11) | C2 |
9 | 411.3.3 | All sockets rated at 20 amps or less throughout the property require additional RCD protection having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn unless it is a circuit supplying a socket(s) that is/are specifically labelled or otherwise suitably identified for a connection of a particular item(s) of equipment. Regulation 411.3.3 (soi6.17.2) | C3 |
10 | 411.3.3 | All sockets that maybe used to supply portable equipment outside of the equipotential area require additional RCD protection having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn. Regulations 411.3.3 & 415.1.1 (soi6.17.1) | C2 |
11 | 132.14.1 | An independently operated single pole protective device (not part of a double pole MCB) has been installed in the neutral conductor. Regulations 132.14.1 & 530.3.2 (soi5.23) | C2 |
12 | 314.1 | An RCD protects the whole installation, due to the sensitivity of this device it is poor practice to protect the whole installation - if it operates the loss of complete power, which, especially at night could lead to injury due to lack of lighting. Regulation 314.1 | C3 |
13 | 421.1.3 | Arc shield(s) missing on protective device(s). Regulation 421.1.3 (soi5.22) | C2 |
14 | 411.3.1.1 | Armour cable gland(s) loose - (armouring not being used as a protective conductor). (soi6.21.4) | C3 |
15 | 543.2.6 | Armour cable gland(s) loose - armouring being used as a protective conductor. Regulation 543.2.6 (soi6.21.4) | C2 |
16 | 526.1 | Armoured cable gland(s) do not have earth washer(s) bolted to the equipment. Regulations 526.1 & 543.2.5 (soi6.21.4) | C3 |
17 | 526.1 | Armoured cable gland(s) do not have star and/or earth washer(s) bolted to the equipment where there is risk of loosening due to vibration. Regulations 526.1, 543.2.5 & Appendix 5 (soi6.21.4) | C3 |
20 | 528.1 | Band I voltage cable(s) that are not insulated for the highest voltage present contained within the same wiring system as Band II low voltage (greater than 50V and less than or equal to 600V Uo a.c or greater than 120V and less than or equal to 900V between conductors and earth) - requires mechanical separation. Regulation 528.1 (soi6.19) | C2 |
21 | 416.2.1 | Blank(s) missing on spare fuse ways - live parts exposed to touch. Regulation 416.2.1 (soi5.4) | C1 |
22 | 416.2.1 | Blind grommet(s) required on electrical distribution equipment – subject to the requirement shall be provided with at least a degree of protection IP2X, IPXXB, IP4X or IPXXD. Regulations 416.2.1 or 416.2.2 (soi5.5) | C2 |
23 | 132.5.2 | Cable(s) and/or wiring systems complete with cable accessories (glands etc.) appropriate to Zone 1 or Zone 2 hazardous areas required where they pass through or terminate in locations having potentially explosive atmospheres. Regulation 132.5.2 (soi6.12) | C2 |
24 | 522.6.101 | Cable(s) concealed in a wall or partition at a depth of less than 50.00mm not installed within the required zone and not having an earthed metallic covering, enclosed in earthed conduit, trunking or ducting, or mechanically protected against penetration of the cable(s) by nails, screws etc. Regulation 522.6.101 (soi6.15) | C3 |
25 | 522.8.4 | Cable(s) hanging loose. Regulations 522.8.4 & 522.8.5 (soi6.2) | C3 |
26 | 522.8.4 | Cable(s) have been installed in long vertical runs of trunking and are at risk of damage due to their weight or it's weight damaging other cable(s), cable(s) require support by suitable means at appropriate intervals. Regulations 522.8.4 & 522.8.5 (soi6.2) | C3 |
27 | 526.2 | Cable(s) have been trimmed (cores cut) to allow termination. Regulation 526.2 (iii) (soi6.6) | C2 |
28 | 522.2.1 | Cable(s) in equipment/accessory(s) are showing signs of burning/overheating due to adjacent heat source(s). Regulation 522.2.1 (soi6.7) | C2 |
29 | 522.2.100 | Cable(s) in equipment/accessory(s) are showing signs of burning/overheating due to internal components(s). Regulation 522.2.100 (soi6.7) | C2 |
30 | 522.2.100 | Cable(s) in fluorescent fitting(s) are showing signs of burning/overheating due to internal component(s). Regulation 522.2.100 (soi6.7) | C2 |
31 | 559.6.2 | Cable(s) in fluorescent/luminaires fittings used for “through wiring” are showing signs of burning/overheating. Regulation 559.6.2 (soi6.7) | C2 |
32 | 522.2.100 | Cable(s) in luminaire fitting(s) are showing signs of burning/overheating due to internal component(s). Regulation 522.2.100 (soi6.7) | C2 |
33 | 522.6.1 | Cable(s) insulation damaged (not exposing live conductors). Regulation 522.6.1 (soi6.3) | C3 |
34 | 416.1 | Cable(s) insulation damaged by rodents exposing live conductors. Regulation 416.1 & 522.10.1 (soi6.3) | C1 |
35 | 416.1 | Cable(s) insulation damaged exposing live conductors. Regulations 416.1 & 522.6.1 (soi6.3) | C1 |
36 | 528.3.2 | Cable(s) or wiring system positioned below services such as water, steam or gas liable to be at risk from condensation. Regulation 528.3.2 (soi6.12) | C3 |
37 | 528.3.1 | Cable(s) or wiring system(s) at risk of damage due to being within the vicinity of services that produce heat, smoke or fumes. Regulation 528.3.1 (soi6.12) | C2 |
38 | 527.1.1 | Cable(s) or wiring systems are installed in roof spaces having a thatch roof require mechanical protection e.g steel conduit, steel trunking etc. or requires additional protection against insulation faults by an RCD(s) having a rated residual operating current (IΔn) =<300mA due to the enhanced fire risk especially where rodents may cause damage. Regulations 527.1.1 & 532.1 (soi6.12) | C3 |
39 | 522.10.1 | Cable(s) or wiring systems showing signs of damage by fauna (rodents) Regulation 522.10.1 (soi6.12) | C3 |
40 | 523.9 | Cable(s) or wiring systems where being loaded to near full capacity, at risk of over-heating due to being surrounded by thermal insulation. Regulation 523.9 (soi6.8) | C2 |
41 | 522.8.4 | Cable(s) require support. Regulations 522.8.4 & 522.8.5 (soi6.2) | C3 |
42 | 134.1.3 | Conductor(s) require correct phase identification. Regulations 134.1.3 & 514.3.1 (soi6.1) | C3 |
43 | 514.3.1 | Conductor(s) require phase identification. Regulations 134.1.3 & 514.3.1 (soi6.1) | C3 |
44 | 526.2 | Cable(s) showing signs of burning. Regulation 526.2 (v) (soi6.7) | C2 |
45 | 526.2 | Cable(s) showing signs of over heating/burning. Regulation 526.2 (v) (soi6.7) | C2 |
46 | 522.6.103 | Cable(s) that are concealed in partition walls with which the internal construction includes metallic parts other than metallic fixings such as nails, screws etc. irrespective of the depth of the cable(s) and not intended to be under the supervision of a skilled or instructed person, all cable(s) not having an earthed metallic covering, enclosed in earthed conduit, trunking or ducting require additional protection provided by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn. Regulation 522.6.103 (soi6.15) | C3 |
47 | 522.8.4 | Cable(s) unsupported. Regulations 522.8.4 & 522.8.5 (soi6.2) | C3 |
48 | 416.2.1 | Casing damaged - live parts exposed to touch. Regulations 416.2.1, 421.7 & 526.5 (soi6.21.3) | C1 |
49 | 521.8.2 | Circuit (230 volt) wired/connected across 2 - phases (400 volt). Regulation 521.8.2 (soi6.22) | C1 |
50 | 526.3 | Circuit leaves electrical equipment in one type of cable and ends in another type - joint inaccessible. Regulation 526.3 (soi6.22) | FI |
51 | 514.9.1 | Circuit not located - requires tracing, identifying and source labelling up. Regulation 514.9.1 (soi5.17) | FI |
52 | 514.4.2 | Circuit protective conductor(s) require sleeving. Regulations 134.1.3, 514.4.2 & 514.4.6 (soi6.1) | C3 |
53 | 525.101 | Circuit too long in respect of load and cable size (voltage drop). Regulation 525.101 & Appendix 12 (soi6.11) | C2 |
54 | 543.7.1.103 | Circuit(s) supplying multiple number of items giving rise to risk of high protective conductor currents greater than 10mA require a high integrity protective connection. Regulation 543.7.1.103 (soi6.10) | C2 |
55 | 543.2.5 | Conduit used as a circuit protective conductor badly corroded. Regulation 543.2.5 (soi3.1.4) | C2 |
56 | 543.2.5 | Conduit used as a circuit protective conductor having joints that are showing signs of corrosion and deterioration. Regulation 543.2.5 (soi3.1.4) | C3 |
57 | 521.10.1 | Conduit(s) damaged exposing non-sheathed cable(s). Regulation 521.10.1 (soi6.4) | C3 |
58 | * | Conduit(s) damaged. (soi6.22) | C3 |
59 | 543.3.6 | Conduit(s) have loose joints. Regulation 543.3.6 (soi3.1.4) | C3 |
60 | 432.4 | Copper wire has been inappropriately used as a protective device where fault and/or overload protection is required. Regulations 432.4 & 433.1.1 (soi6.9) | C2 |
61 | 522.6.4 | Cover missing on electrical equipment (not exposing live parts). Regulation 522.6.4 | C3 |
62 | 416.2.1 | Cover missing on electrical equipment exposing live parts. Regulations 416.2.1, 421.7 & 526.5 (soi6.21.3) | C1 |
63 | 416.2.1 | Cover missing on junction/terminal box – live parts accessible. Regulation 416.2.1 (soi6.21.3) | C1 |
64 | 521.10.1 | Cover(s) missing on conduit box(s) exposing non-sheathed cable(s). Regulation 521.10.1 (soi6.4) | C3 |
65 | 134.1.3 | CPC sleeving required in accessory(s). Regulations 134.1.3, 514.4.2 & 514.4.6 (soi6.1) | C3 |
66 | 134.1.3 | CPC sleeving required in electrical equipment. Regulations 134.1.3, 514.4.2 & 514.4.6 (soi6.1) | C3 |
67 | 411.3.1.1 | CPC(s) require continuing through insulated enclosure(s). Regulation 411.3.1.1 (soi6.10) | C2 |
68 | 537.4.2.6 | Device(s) for emergency isolating/switching require having the capability of latching or being restrained in the “off” or “stop” position unless both the means of emergency switching and re-energizing are under the control of the same person. The release of an emergency switching device shall not re-energize the the relevant part(s) e.g it requires another action to energize the relevant part(s). Regulation 537.4.2.6 (soi7.3.3) | C2 |
69 | 537.4.2.5 | Device(s) for emergency isolating/switching require to be readily accessible at locations where a danger might occur, and where appropriate, at any other additional locations where the danger can be removed. Regulation 537.4.2.5 (soi7.3.2) | C2 |
70 | 537.4.2.4 | Device(s) for emergency isolating/switching requires clear identification, preferably by the colour red with a contrasting background. Regulation 537.4.2.4 (soi7.3.5) | C3 |
71 | 542.3.2 | Earth rod requires mechanical protection. Regulation 542.3.2 (soi3.1.2) | C3 |
72 | 526.3 | Earth rod requires to be accessible for inspection, testing and maintenance. Regulation 526.3 (soi3.1.2) | C3 |
73 | 134.1.3 | Earth sleeving required in accessory(s). Regulations 134.1.3, 514.4.2 & 514.4.6 (soi6.1) | C3 |
74 | 134.1.3 | Earth sleeving required in electrical equipment. Regulations 134.1.3, 514.4.2 & 514.4.6 (soi6.1) | C3 |
75 | 411.3.1.1 | Earthing required for gland plate. Regulation 411.3.1.1 (soi6.10) | C3 |
76 | 411.3.1.1 | Earthing required for removable door/cover. Regulation 411.3.1.1 (soi6.10) | C3 |
77 | 411.3.1.1 | Earthing required for removable gland plate. Regulation 411.3.1.1 (soi6.10) | C3 |
78 | 132.5.2 | Electrical accessories approved for use in Zone 1 or Zone 2 locations required for areas at risk of fire or potentially explosive atmospheres - environmental conditions. Regulation 132.5.2 (soi6.25) | C2 |
79 | 522.6.4 | Electrical equipment / accessory(s) - damaged (not exposing live parts). Regulation 522.6.4 | C3 |
80 | 416.2.1 | Electrical equipment / accessory(s) broken exposing live parts. Regulations 416.2.1, 421.7 & 526.5 (soi6.21.3) | C1 |
81 | 522.5.1 | Electrical equipment / accessory(s) rusted. (soi6.25) | C3 |
82 | 420.1 | Electrical equipment / accessory(s) showing signs of burning. Regulation 420.1 (ii) (soi6.24) | C2 |
83 | 512.2.4 | Electrical equipment / accessory(s) suffering from ingress of excessive dust – risk of overheating cables or components or effecting the operation of equipment (e.g MCBs, contactors etc.) Regulation 512.2.4 (soi5.5) | C3 |
84 | 522.5.1 | Electrical equipment / accessory(s) too close to water supply. (soi6.25) | C3 |
85 | 132.5.2 | Electrical equipment approved for use in Zone 1 or Zone 2 locations required for areas at risk of fire or potentially explosive atmospheres - environmental conditions. Regulation 132.5.2 (soi6.25) | C2 |
86 | 512.1.2 | Electrical equipment current rating lower than the protective device protecting it. Regulation 512.1.2 | C2 |
87 | 416.2.1 | Electrical equipment lid(s) requires fixing screws – risk of exposed live parts. Regulation 416.2.1 (soi6.21.3) | C1 |
88 | 416.2.1 | Electrical equipment lid(s) requires fixing screws. Regulation 416.2.1 (soi6.21.3) | C3 |
89 | 132.15.1 | Electrical equipment main switch damaged. Regulations 132.15.1 & 537.1.4 (soi5.9) | C2 |
90 | 132.15.1 | Electrical equipment main switch in-operable. Regulations 132.15.1 & 537.1.4 (soi5.9) | C2 |
91 | 537.2.2.2 | Electrical equipment main switch requires "On - Off" legend. Regulation 537.2.2.2 (soi5.21) | C3 |
92 | 514.9.1 | Electrical equipment marked incorrectly. Regulation 514.9.1 (soi5.17) | C3 |
93 | 422.4.1 | Electrical equipment mounted on combustible material requires insulated back plate. Regulation 422.4.1 (soi5.6) | C2 |
94 | 416.2.1 | Electrical equipment panel does not lock, door is insecure – exposed live parts accessible. Regulation 416.2.1 (soi5.4) | C1 |
95 | 416.2.1 | Electrical equipment panel does not lock, door is insecure. Regulation 416.2.1 (soi5.4) | C3 |
96 | 512.2.1 | Electrical equipment positioned below services (such as water, steam or gas services) liable to be at risk from condensation. Regulation 512.2.1 (soi6.25) | C2 |
97 | 512.1.2 | Electrical equipment rated lower than protective device backing it. Regulation 512.1.2 | C3 |
98 | 526.1 | Electrical equipment requires an earthing terminal bar and all earth’s connecting to it. Regulation 526.1 (soi3.1) | C3 |
99 | 530.4.1 | Electrical equipment requires mounting in a permanent fashion or re-fixing where it has become loose. Regulation 530.4.1 (soi5.2) | C3 |
100 | 132.15.1 | Electrical equipment switch/isolator damaged. Regulations 132.15.1 & 537.2.2.1 (soi5.9) | C2 |
101 | 542.4.1 | Electrical installation and/or sections of require a main earthing terminal or bar. Regulation 542.4.1 (soi3.1) | C3 |
102 | 526.2 | Electrical part(s) showing signs of arcing. Regulation 526.2 (soi6.24) | C2 |
103 | 537.4.1.1 | Emergency isolation/switching required to isolate the supply to remove an unexpected dangerous condition or occurrence. Regulation 537.4.1.1 (soi7.3.1) | C2 |
104 | 537.3.1.1 | Emergency light(s) require local isolation for maintenance and testing purposes. Regulation 537.3.1.1 (soi7.2.1) | C3 |
105 | 132.15.1 | Equipment having electric motor(s) require means of isolation which is readily accessible, easily operated and placed so as to prevent danger. Regulation 132.15.1 (soi7.3.1) | C2 |
106 | 416.2.4 | Exposed live parts accessible without the use of a key or tool. Regulation 416.2.4 (soi5.4) | C1 |
107 | 414.4.4 | Exposed-conductive-parts of a SELV circuit(s) have been connected to Earth or to a CPC or exposed-conductive-part(s) of another circuit. Regulation 414.4.4 (soi3.2.1) | C2 |
108 | 553.1.7 | More socket-outlet(s) required where multi-way adaptor(s), extension lead(s), trailing socket(s) etc. are being used for semi-permanent equipment/appliances. Multi-way adaptors, extension leads etc. are at risk from overheating and mechanical damage and with regard to extension leads etc. are a tripping hazard. Where multi-way adaptor(s), extension lead(s), trailing socket(s) etc. are being used these items should never be left unattended and require to be visible and accessible throughout their length. Regulation 553.1.7 (soi6.22) | C3 |
109 | 560.8.1 | Fire alarm cables reliant on PVC supports (may include PVC containment – trunking, conduits etc.) and not supported using metallic systems. Regulation 560.8.1 (soi6.2) | C2 |
110 | 560.7.1 | Fire alarm panel requires wiring on separate circuit wired from the electricity supply in-comer position. Regulation 560.7.1 (soi6.12) | C3 |
111 | 560.8.1 | Fire alarm panel supply requires wiring in fire resistant cable. Regulation 560.8.1 (soi6.12) | C3 |
112 | 543.2.6 | Flexible conduit being used as a cpc. Regulation 543.2. (soi6.10) | C2 |
113 | 521.10.1 | Flexible conduit damaged exposing non-sheathed cable(s). Regulations 521.10.1 & 522.6.1 (soi6.4) | C3 |
114 | 522.6.1 | Grommets required on accessory metal back boxes. Regulation 522.6.1 (soi6.21.4) | C3 |
115 | 522.6.1 | Grommets required on electrical equipment. Regulation 522.6.1 (soi5.24) | C3 |
116 | * | Guard(s) missing on motor(s). | C5 |
117 | * | Guard(s) missing on pulley belt(s). | C5 |
118 | 522.1.1 | Heat resistant cable required. Regulation 522.1.1 (soi6.23) | C2 |
119 | 132.5.1 | I.P rated accessory(s) required for the protection against weather, corrosive atmospheres or other adverse conditions - environmental conditions. Regulation 132.5.1 (soi6.25) | C2 |
120 | 132.5.1 | I.P rated electrical equipment required for the protection against weather, corrosive atmospheres or other adverse conditions – environmental conditions. Regulation 132.5.1 (soi6.25) | C2 |
121 | 522 | I.P rated wiring system required for the protection against external influences. Regulation 522 (soi6.12) | C3 |
122 | 526.2 | Inappropriate cable lug(s) used. Regulation 526.2 (soi6.6) | C3 |
123 | 416.2.1 | Inappropriate connector(s) used above ceiling for light fitting(s). Regulations 416.2.1, 421.7 & 526.5 (soi6.6) | C3 |
124 | 416.2.1 | Inappropriate connector(s) used in trunking. Regulations 416.2.1, 421.7 & 526.5 (soi6.6) | C3 |
125 | 132.12 | Insufficient accessibility to electrical equipment where other services have been installed. Regulation 132.12 (soi5.1) | C3 |
126 | 132.12 | Insufficient accessibility to electrical equipment. Regulation 132.12 (soi5.1) | C3 |
127 | 411.3.1.1 | Insulated gland plate requires earthing from metallic cable glands to earth terminal. Regulation 411.3.1.1 (soi6.10) | C3 |
128 | 537.3.2 | Isolator/switch requiring manual operation with the open contacts being clearly visible or reliably indicated, designed and/or installed as to prevent inadvertent or unintentional switching on (able to be locked off), sited for convenient access and durably marked for identification required for mechanical maintenance. Regulation 537.3.2 (soi7.2.3, soi7.2.4, soi7.2.5, soi7.2.2) | C2 |
129 | 512.2.1 | It is recommended that socket-outlet(s) are mounted above sink height at a horizontal distance not less than 300mm from the edge of the sink top. Regulation 512.2.1 (soi6.25) | C3 |
130 | 526.3 | Junction boxes utilizing screw terminals must be accessible for inspection, testing & maintenance. Regulation 526.3 | C3 |
131 | 421.1.2 | Light fittings mounted in ceilings require smoke hoods to prevent fire and spread of harmful smoke from penetrating the ceiling void and retaining the ceiling's fire protection integrity. Regulation 421.1.2 (soi8.7.2) | C2 |
132 | 422.3.1 | Light fittings mounted too close to combustible materials. Regulations 422.3.1 & 422.4.2 (soi8.7.3) | C2 |
133 | 411.3.1.1 | Lighting circuit (or part there of) - absence of a circuit protective conductor for a circuit having class I or "non-insulated" accessories. Regulation 411.3.1.1 (soi6.10) | C2 |
134 | 412.2.3.2 | Lighting circuit (or part there of) - absence of a circuit protective conductor for a circuit having only class II or "all insulated" accessories. Regulation 412.2.3.2 (soi6.10) | C3 |
135 | 559.6.1.6 | Lighting circuit(s) incorporating bayonet lamp holders B15 or B22 and Edison screw lamp holders shall be protected by an over-current protective device not exceeding 16A. Regulation 559.6.1.6 (soi6.9) | C2 |
136 | 416.2.1 | Live parts require to be inside enclosures or behind barriers providing a minimum degree of protection of IPXXB where live parts can be touched. Regulation 416.2.1 (soi5.5) | C1 |
137 | 132.15.1 | Local isolation required for prevention of equipment being inadvertently or unintentionally energized. Regulations 132.15.1 & 537.2.1.2 (soi7.1.1) | C2 |
138 | 537.2 | Local isolation required. Regulation 537.2 (soi7.1.1) | C2 |
139 | 537.4.1.1 | Local means of isolation required for emergency purposes. Regulation 537.4.1.1 (soi7.3.1) | C2 |
140 | 422.3.9 | Locations where there is risk of fire due to the nature of processed or stored materials, (with the exception of mineral insulated cables, busbar trunking systems and powertrack systems), cables and wiring systems (conduit, trunking etc.) require additional protection against insulation faults by RCD(s) having a rated residual operating current (IΔn) =<300mA. Regulation 422.3.9 (soi5.13) | C2 |
141 | 422.3.8 | Locations where there is risk of fire due to the nature of processed or stored materials, every luminaire requires to be appropriate for the location, to be enclosed with a degree of protection to a minimum of IP5X, to have a limited surface temperature in accordance with BS EN 60598-2-24 and be of a type that prevents lamp components from falling from the luminaire. Regulation 422.3.8 (soi8.7.2) | C2 |
142 | 414.4.3 | Luminaire supporting coupler(s) on a SELV or PELV system have been used where they are compatible with other plugs on other systems (low voltage). Regulation 414.4.3 (soi3.2.2) | C2 |
143 | 521.8.2 | Neutral being shared with other circuit. Regulation 521.8.2 (soi6.11) | C2 |
144 | 134.1.3 | Neutral(s) requires correct phase identification. Regulations 134.1.3 & 514.3.1 (soi6.1) | C3 |
145 | 514.1.2 | Neutrals require to be re-connected in the correct order or marked as per Regulation 514.5.1 so that there is no possibility of confusion. Regulation 514.1.2 (soi6.1) | C3 |
146 | 521.10.1 | Non-sheathed cable(s) exposed on conduit system. Regulation 521.10.1 (soi6.4) | C3 |
147 | 521.10.1 | Non-sheathed cable(s) exposed on trunking system. Regulation 521.10.1 (soi6.4) | C3 |
148 | 521.5.1 | Phases entering ferrous equipment through different holes. Regulation 521.5.1 (soi5.25) | C2 |
149 | 414.4.3 | Plug(s) and socket-outlet(s) on a SELV system have a protective conductor contact. Regulation 414.4.3 (soi4.7) | C2 |
150 | 533.1.1.2 | Protective device(s) - cartridge type fuses replaced with fuse wire. Regulation 533.1.1.2 (soi6.9) | C2 |
151 | 416.2.1 | Protective device(s) damaged exposing live terminals. Regulation 416.2.1 (soi5.3) | C1 |
152 | 416.2.1 | Protective device(s) removed exposing live terminals. Regulation 416.2.1 (soi5.3) | C1 |
153 | 421.1.3 | Protective device(s) require arc shield(s). Regulation 421.1.3 (soi5.22) | C2 |
154 | 514.8.1 | Protective device(s) require labelling with circuit descriptions. Regulation 514.8.1 (soi5.17) | C3 |
155 | 514.8.1 | Protective device(s) require labelling with correct circuit descriptions. Regulation 514.8.1 (soi5.17) | C3 |
156 | 543.7.1.103 | Radial circuits (including spur sockets connected to a ring main) require earthing improvements (high integrity protective connection) where the total protective current is likely to exceed 10mA (e.g supplying multiple PCs or high frequency fluorescent light fittings). Regulation 543.7.1.103 (soi3.1.3) | C2 |
157 | 531.2.9 | RCD does not discriminate with RCD up-line on electrical system (two or more RCDs in series), where discrimination in their operation is required to prevent danger. Regulation 531.2.9 | C2 |
158 | 433.1.103 and Appendix 15 | Ring main – electrical equipment with a power rating exceeding 2kW required to have their own dedicated circuit due to risk of overload. Regulation 433.1.103 and Appendix 15 (soi6.11) | C2 |
159 | 433.1 | Ring main has spurred sockets wired from spurred sockets without a fused connection unit being used for overload protection at the source of the first spur. Regulation 433.1 & Appendix 15 (soi6.11) | C2 |
160 | 521.10.1 | Secondary insulation of cable(s) not brought into electrical equipment - inner insulation showing although not accessible to touch or likely to come into contact with metal work. Regulation 521.10.1 (soi6.21.2) | C3 |
161 | 521.10.1 | Secondary insulation of cable(s) not brought into electrical equipment – inner insulation showing and accessible to touch and/or likely to come into contact with metal work. Regulations 521.10.1, 522.6.1 & 522.8.1 (soi6.21.2) | C2 |
162 | 543.3.1 | Shroud(s) required on armoured cable(s). Regulation 543.3.1 (soi6.21.4) | C3 |
164 | 543.7.1.104 | Socket outlets require two separate earth terminals to enable earth wires to be connected independently where the total protective current is likely to exceed 10mA (e.g where sockets are supplying multiple PCs and associated equipment). Regulation 543.7.1.104 (soi3.1.4) | C2 |
165 | 543.7.2.101 | Socket ring main circuit(s) supplying equipment where the total protective current is likely to exceed 10mA (e.g supplying multiple PCs and associated equipment) and where two protective conductors are used in accordance with Regulation 543.7.1.103 require terminating independently of each other at all connection points including the distribution board. Requires all accessories to have two separate earth terminals. Regulation 543.7.2.101 (soi3.1.4) | C2 |
166 | 553.1.6 | Socket-outlet(s) mounted too low, risk of mechanical damage to the socket-outlet(s) or to plugs and their flexible cords where damage may occur during insertion, use or withdrawal. Regulation 553.1.6 (soi6.25) | C3 |
167 | 414.4.3 | Socket-outlet(s) on a SELV or PELV system have been used where they are compatible with other plugs on other systems (low voltage). Regulation 414.4.3 (soi3.2.2) | C2 |
168 | 553.1.7 | Socket-outlet(s) require to be conveniently accessible and installed adjacent to mobile equipment. Regulation 553.1.7 (soi7.1.2) | C3 |
169 | 415.1.1 | Socket(s) being used for entertainment purposes in respect of an entertainment licence require additional RCD protection having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn. Regulation 415.1.1 (soi5.11) | C2 |
170 | 701.415.2 | Supplementary equipotential bonding required in a location containing a bath or shower in a building having a protective equipotential bonding in accordance with Regulation 411.3.1.2 and where all the following conditions have not been met, (i) Regulation 411.3.2 All circuits comply with the requirements for automatic disconnection within the location. (ii) Regulation 701.411.3.3. All circuits in the location have additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn. (iii) Regulation 411.3.1.2 All extraneous-conductive-parts within the location are connected effectively to the protective equipotential bonding. Regulation 701.415.2 (soi9.4, soi9.0) | C2 |
171 | 560.7.5 | Supply for the fire alarm panel requires wiring from the electricity supply in-comer position in a location accessible to skilled or instructed persons only with a 1 - way fuse unit coloured red with a label "Fire alarm panel - Do Not switch Off". Regulation 560.7.5 (soi7.1.1) | C3 |
173 | 132.15.1 | Switch inter-lock has been disconnected from the spindle - switch indicating "Off" while the unit is in the on position. Regulations 132.15.1, 537.2.2.1 & 537.2.2.2 (soi7.1.1, soi7.1.3, soi7.1.4) | C2 |
175 | 411.3.3 | T.T. earthing system require all sockets to have RCD protection having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn. Regulation 411.3.3 (soi5.12) | C2 |
176 | 526.5 | Tape joint(s) require correct termination. Regulation 526.5 (soi6.21.3) | C2 |
177 | 526.2 | Terminal(s) showing signs of arcing. Regulation 526.2 (soi6.24) | C2 |
178 | 416.2.1 | The sides and bottom of any enclosures or barriers containing live parts require a minimum degree of protection of at least IP2X. Regulation 416.2.1 (soi5.5) | C2 |
179 | 521.10.1 | Trunking lid(s) missing exposing non-sheathed cable(s). Regulation 521.10.1 (soi6.4) | C3 |
180 | 543.2.6 | Trunking used as a circuit protective conductor badly corroded Regulation 543.2.6 (soi3.1.4) | C2 |
181 | 543.2.6 | Trunking used as a circuit protective conductor having joints that are showing signs of corrosion and deterioration. Regulation 543.2.6 (soi3.1.4) | C2 |
182 | 522.6.101 | Unable to ascertain whether cable(s) concealed in a wall or partition at a depth of less than 50.00mm not installed within the required zone and not having an earthed metallic covering, enclosed in earthed conduit, trunking or ducting, or mechanically protected against penetration of the cable(s) by nails, screws etc. Regulation 522.6.101 (soi6.15) | FI |
183 | 526.3 | Unable to remove cover on electrical equipment. Regulation 526.3 (soi5.1) | C3 |
184 | 131.2.1 | Unused cables require disconnecting from the fuse way(s) and removing completely or connecting down to earth at both beginning and end of circuit (where they are exposed conductors not enclosed in an item of electrical equipment or insulated which may give rise to a shock due to induced current). Regulation 131.2.1 (soi6.3) | C2 |
185 | 514.16 | Warning label – "Danger – circuit(s) having high protective current within" required. Regulations 514.16 & 543.7.1.5 (soi5.21) | C3 |
186 | 514.11.1 | Warning label(s) - "Danger - more than one point of isolation" required. Regulation 514.11.1 & 537.2.1.3 (soi5.21) | C3 |
188 | 514.14.1 | Warning label(s) - "This installation has wiring colours to two versions of BS 7671. Great care should be taken before undertaking extension, alteration or repair that all conductors are correctly identified." required. Regulation 514.14.1 (soi5.18) | C3 |
190 | 514.10.1 | Warning label(s) - 400 volt warning notice(s) required on equipment where the voltage is greater than 230V. Regulation 514.10.1 (soi5.21) | C3 |
191 | 514.10.1 | Warning label(s) - 400 volt warning notice(s) required. Regulation 514.10.1 (soi5.21) | C3 |
192 | 514.12.2 | Warning label(s) - RCD test label required at or near the origin of the supply. Regulation 514.12.2 (soi5.16) | C3 |
193 | 514.13.1 | Warning label(s) – "Safety Electrical Connection - Do Not Remove" required for equipotential bonding connections. Regulation 514.13.1 (soi3.1.9) | C3 |
194 | 527.2.3 | Where metal (non-flame propagating) wiring systems such as conduit, trunking, ducting etc. having an internal cross-sectional area >710.00mm (>32.00mm diam. conduit) penetrate ceilings, walls, floors etc. of the building construction which has a specified fire-resistance, the wiring system requires sealing internally to the same specification of the fire resistance specified before penetration. Regulation 527.2.3 (soi6.18) | C3 |
195 | 522.6.102 | Where the electrical installation is not intended to be under the supervision of a skilled or instructed person all cables that are encased within solid or stud walls and do not have earthed metallic protection require additional protection provided by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn. Regulation 522.6.102 (soi6.16) | C3 |
197 | 431.2.1 | Where the neutral conductor has a cross-sectional area less than the cross-sectional area of the line conductors it is required that the neutral conductor is provided with over-current protection appropriate to the size of the neutral conductor. The neutral over-current detection is required to disconnect all of the line conductors, but not necessarily the neutral conductor. Regulation 431.2.1 (soi6.11) | C2 |
198 | 527.2.1 | Where wiring and wiring system(s) passes through openings or holes made to allow passage through walls, ceilings, floors etc. the openings or holes require sealing where the integrity of the fire resistance has been compromised. Regulation 527.2.1 (soi6.18) | C2 |
199 | 522.3.1 | Wiring system(s) (cables, conduit, trunking etc.) suffering damage caused by ingress of water or condensation – requires appropriate I.P rated systems for the environment. Regulation 522.3.1 (soi6.12) | C3 |
200 | 522.5.1 | Wiring system(s) (cables, conduit, trunking etc.) suffering damage caused by the presence of corrosive or polluting substances including water. Regulation 522.5.1 (soi6.12) | C3 |
201 | 514.11 | Warning label(s) – “This item of equipment has exposed conductive parts when cover removed – isolate using locking device upstream before removing cover” required where cover can only be removed by unlocking or with the use of a tool. Regulation 514.11 (soi5.21) | C3 |
202 | 411.8.5 | Socket-outlet(s) on a Reduced Low Voltage system have been used where they are compatible with other plugs on other systems (low voltage). Regulation 411.8.5 (soi3.3.2) | C2 |
203 | 411.8.3 | All line conductors on a Reduced Low Voltage system require overcurrent or RCD protection for fault protection. Regulation 411.8.3 (soi6.11) | C2 |
204 | 411.8.4 | The adequacy of source for a Reduced Low Voltage System has not been met. Regulation 411.8.4 (soi3.3.1) | C2 |
205 | 411.8.3 | All exposed-conductive-parts of a Reduced Low Voltage System require connecting to earth. Regulation 411.8.3 (soi6.10) | C2 |
206 | 134.1.5 | The electricity supplier cut-out/fuse requires attention – suspect overloaded or running warm due to loose connection(s) . Regulation 134.1.5 (soi1.2) | C2 |
207 | 134.1 | The electricity supplier cut-out/fuse requires attention - risk from exposed parts. Regulation 134.1 (soi1.2) | C1 |
208 | 134.1.5 | The electricity supplier meter cables (tails) require attention – suspect overloaded or running warm due to loose connection(s) where connected to the electricity supplier meter. Regulation 134.1.5 (soi1.3) | C2 |
209 | 134.1.5 | The consumer meter cables (tails) require attention – suspect overloaded or running warm due to loose connection(s) where connected to the electricity supplier meter. Regulation 134.1.5 (soi1.4) | C2 |
210 | 416.2.1 | The electricity supplier meter equipment requires attention having exposed connections. Regulation 416.2.1 (soi1.5) | C1 |
211 | 134.1.5 | The electricity supplier meter equipment requires attention – suspicion of loose connections. Regulation 134.1.5 (soi1.5) | C2 |
212 | 551.6.1 | Adequate isolation arrangements required for parallel or switched alternative sources required. Regulation 551.6.1 (soi2.0) | C2 |
213 | 543.3.2 | Unable to gain access to the earthing conductor connection. Regulation 543.3.2 (soi3.1.5) | C3 |
214 | 544.1.2 | Where practicable main equipotential bonding conductor(s) require connecting within 600mm of the meter outlet union or at the point of entry to the building if the meter is external and before any branch pipework. Regulation 544.1.2 (soi3.1.7) | C3 |
215 | 543.3.2 | Unable to gain access to the main protective bonding conductor(s) connection. Regulation 543.3.2 (soi3.1.8) | C3 |
216 | 134.1.1 | Distribution equipment loose. Regulation 134.1.1 (soi5.2) | C3 |
217 | 133.3 | Electrical enclosure has been damaged so as to impair safety from shock risk. Regulation 133.3 (soi5.7) | C1 |
218 | 537.1.4 | Where a main switch (main isolator for the installation) is intended to be used by ordinary person(s) e.g household or a similar installation all live conductors (the neutral is a live conductor) shall be switched. Regulation 537.1.4 (soi5.8) | C3 |
219 | 612.13.2 | Unable to manually operate circuit-breaker(s) – functional check. Regulation 612.13.2 (soi5.14) | C2 |
220 | 612.13.2 | RCD/RCBOs will not operate manually – functional check. Regulation 612.13.2 (soi5.15) | C2 |
221 | 612.13.1 | RCD will not operate on it's integral test button – functional check Regulation 612.13.1 (soi5.15) | C2 |
222 | 514.15.1 | Warning notice(s) required where there are alternative means of supply at the appropriate locations. Regulations 514.15.1 (soi5.19) | C3 |
223 | 522 | Flexible conduit damaged. Section 522 (soi6.5) | C2 |
224 | 522.11.1 | Where cables are exposed to direct sunlight they are required to be of the correct type or protected against solar and/or ultraviolet radiation. Regulation 522.11.1 (soi6.13) | C3 |
225 | 522.6.101 | Unable to ascertain whether concealed cable(s) are installed in the correct zone. Regulation 522.6.101 (v) (soi6.14) | FI |
226 | 528.3.1 | Cable(s) require segregating or separating from non-electrical services. Regulation 528.3 (soi6.20) | C3 |
227 | 526.6 | Due to the method of installation or lack of support of cables, connections of conductors are being placed under strain. Regulation 526.6 (soi6.21.1) | C2 |
228 | 537.2.1.2 | Isolators for general isolation not local to the item off equipment require the ability to be secured in the OFF position. Regulation 537.2.1.2 (soi7.1.3) | C3 |
229 | 537.2.2.6 | Isolators for general isolation require clear identification by position and/or durable markings. Regulation 537.2.2.6 (soi7.1.5) | C3 |
230 | 514.11.1 | Warning label required where live parts cannot be isolated by the operation of a single device (having more than one source of supply). Regulation 514.11.1 (soi7.1.6) | C3 |
231 | 416.2.1 | Enclosure of a fixed item of current using equipment damaged resulting in exposed-conductive-parts. Regulation 416.2.1 (soi8.3) | C1 |
232 | 421.1 | Possibility of a fire hazard caused by a fixed item of current using equipment due to either position of, or material on which it is fixed. Regulation 421.1 (soi8.2) | C2 |
233 | 512 | Enclosure of a fixed item of current using equipment damaged resulting in risk in terms of it's I.P rating. Section 512 (soi8.1) | C2 |
234 | 512.2.1 | Item of fixed current using equipment not suitable for the environment and external influences in the situation in which it is being used. Regulation 512.2 (soi8.4) | C2 |
235 | 134.1.1 | Item of current using equipment requires a more secure method of fixing. Regulation 134.1.1 (soi8.5) | C2 |
236 | 527.2.1 | Where cable(s) pass through elements of the building structure such as floors, walls, ceilings etc. any openings made require sealing according to the degree of fire-resistance before penetration so as to restrict the spread of fire. Section 527.2.1 (soi8.6) | C2 |
237 | - | Incorrect type of lamps fitted to luminaires. (soi8.7.1) | C2 |
238 | 526.2.(v) | Signs of overheating to conductors and/or terminations in luminaires. Regulation 526.2.(v) (soi8.7.4) | C2 |
239 | 701.414 | Where used as a protective measure for electrical equipment in locations containing a bath or shower the requirements of SELV or PELV has not been met. Regulation 701.414 (soi9.2, soi9.0) | C2 |
240 | 701.512.3 | Shaver socket(s) do not comply with BS EN 61558-2-5 or BS 3535 where positioned in a location containing a bath or shower. Regulation 701.512.3 (soi9.3, soi9.0) | C2 |
241 | 701.512.3 | Low voltage (e.g. 230 volts) socket(s) within 3 metres of the boundary of zone 1 not protected by the measure of electrical separation (isolation transformer). Regulation 701.512.3 (soi9.5, soi9.0) | C2 |
242 | 701.512.2 | Enclosure of a fixed item of current using equipment damaged in a location containing a bath or shower resulting in risk in terms of it's I.P rating. Regulation 701.512.2 (soi9.6, soi9.0) | C2 |
243 | 701.512.2 | Item of electrical equipment not suitable in terms of it's I.P rating for the environment and external influences in locations containing a bath or shower. Regulation 701.512.2 (soi9.6, soi9.0) | C2 |
244 | 701.512.3 | Electrical equipment (switches etc.) not suitable for the particular zone in which it is situated in a location containing a bath or shower. Regulation 701.512.3 (soi9.7, soi9.0) | C2 |
245 | 701.55 | Item(s) of current using equipment (e.g low voltage fan not protected by SELV) not suitable for a particular zone in a location containing a bath or shower. Regulation 701.55 (soi9.8, soi9.0) | C2 |
246 | 702.410.3.4 | All items of electrical equipment, cable(s) and wiring systems within zone(s) of a location containing a swimming pool or other type of basin (e.g fountain) require additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn. Regulation 702.410.3.4 (soi10.1, soi10.0) | C2 |
247 | 702.414 | Where used as a protective measure for electrical equipment in locations containing a swimming pool or other type of basin (e.g fountain) the requirements of SELV or PELV has not been met. Regulation 702.414 (soi10.2, soi10.0) | C2 |
248 | 702.415.2 | All extraneous-conductive-parts in zones 0, 1 & 2 of a location containing a swimming pool or other type of basin (e.g fountain) require connecting by supplementary protective bonding conductors to the protective conductors of exposed-conductive-parts. Regulation 702.415.2 (soi10.3, soi10.0) | C2 |
249 | 702.512.2 | Enclosure of a fixed item of current using equipment damaged in a location containing a swimming pool or other type of basin (e.g fountain) resulting in risk in terms of it's I.P rating. Regulation 702.512.2 (soi10.4, soi10.0) | C2 |
250 | 702.512.2 | Item of electrical equipment not suitable in terms of it's I.P rating for the environment and external influences in locations containing a swimming pool or other type of basin (e.g fountain) for a particular zone. Regulation 702.512.2 (soi10.4, soi10.0) | C2 |
251 | 702.522.23 | for electrical equipment in zone 0 an additional requirement for the wiring of a fountain has not been met where a cable is required to be installed as far outside the basin rim as far as reasonably practicable and/or being run to the electrical equipment inside zone 0 by the shortest practicable route. Regulation 702.522.23 (soi10.5, soi10.0) | C3 |
252 | 702.522.23 | For a cable in zone 1 an additional requirement for the wiring of a fountain has not been met where it is required to be selected, installed and provided with mechanical protection to medium severity (AG2) and/or where submerged in water (AD8) IPX8 (cable type H07RN8-F/BS 7919 for a depth of up to 10 metres, for a depth greater than 10 metres the cable manufacturer requires consulting). Regulation 702.522.23 (soi10.5, soi10.0) | C3 |
253 | 702.53 | Socket(s) within zone 2 of a location containing a swimming pool require additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn or by electrical separation (isolation transformer). Regulation 702.53 (soi10.6, soi10.0) | C2 |
254 | 702.55.1 | Item of current using equipment not suitable for zones 0 and 1 in locations containing a swimming pool or other type of basin (e.g fountain). Regulation 702.55.1 (soi10.7, soi10.0) | C2 |
255 | 702.55.4 | The requirements for low voltage supplied equipment used in zone 1 in locations containing a swimming pool or other type of basin (e.g fountain) have not been met. Regulation 702.55.4 (soi10.8, soi10.0) | C2 |
256 | 702.55.4 | Low voltage lighting equipment within zone 1 of a location containing a swimming pool or other type of basin (e.g fountain) requires additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn and shall be mounted at least 2 metres above the boundary of zone 0 and zone 1 (lowest limit of zone 1). Regulation 702.55.4 (soi10.9, soi10.0) | C2 |
257 | 702.55.3 | Mechanical protection required for electrical equipment within zones 0 and 1 of a fountain. Regulation 702.55.3 (soi10.10, soi10.0) | C3 |
258 | 703.411.33 | All items of electrical equipment, cable(s) and wiring systems within zone(s) of a location containing a sauna heater require additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn. Regulation 703.411.33 (soi11.1, soi11.0) | C2 |
259 | 703.414.4 | Where used as a protective measure for electrical equipment in locations containing a sauna heater the requirements of SELV or PELV has not been met. Regulation 703.414.4 (soi11.2, soi11.0) | C2 |
260 | 703.512.2 | Enclosure of a fixed item of current using equipment damaged in a location containing a sauna heater resulting in risk in terms of it's I.P rating. Regulation 703.512.2 (soi11.3, soi11.0) | C2 |
261 | 703.512.2 | Item of electrical equipment not suitable in terms of it's I.P rating for the environment and external influences in locations containing a sauna heater for a particular zone. Regulation 703.512.2 (soi11.3, soi11.0) | C2 |
262 | 703.52 | The wiring system in a location containing a sauna heater has been installed on the inside of the zones i.e. on the warm side of any thermal insulation or heat-resisting cable has not been used where wiring has been installed on the warm side of the thermal insulation of zones 1 & 3. Regulation 703.52 (soi11.4, soi11.0) | C3 |
263 | 703.52 | Metallic sheaths or metallic conduits are accessible in normal use in a location containing a sauna heater. Regulation 703.52 (soi11.4, soi11.0) | C2 |
264 | 703.537.5 | Only electrical equipment for the connection of sauna equipment as per the instructions of the manufacturer of the sauna heater may be installed within zone 1. Regulation 703.537.5 (soi11.5, soi11.0) | C2 |
265 | 703.537.5 | Electrical equipment (switches, sockets etc.) has been installed inside of the location containing a sauna heater. Regulation 703.537.5 (soi11.5, soi11.0) | C2 |
266 | 704.411.3.1 | A PME earthing system has been used where the reliability of connections of extraneous-conductive-parts (e.g scaffold, exposed service pipes, structural steelwork etc.) being connected to a main earthing terminal cannot be assured. Regulation 704.411.3.1 (soi12.1, soi12.0) | C2 |
267 | 704.410.3.10 | Circuits supplying socket-outlet(s) up to and including 32 amps require additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn or by use of a Reduced Low Voltage System (110v isolation transformer). Regulation 704.410.3.10 (soi12.2, soi12.0) | C2 |
268 | 704.411.3.2.1 | Circuits supplying socket(s) with a rated current exceeding 32 amps require additional protection by an RCD(s) not exceeding 500mA. Regulation 704.411.3.2.1 (soi12.3, soi12.0) | C2 |
269 | 704.522.8.10 | Mechanical protection for cable(s) where crossing a site road or walkway(s) required. Regulation 704.522.8.10 (soi12.4, soi12.0) | C2 |
270 | 704.522.8.10 | The correct type of cables/wiring systems are not being used with regard to flexibility and/or resistance to abrasion or water. Regulation 704.522.8.10 (soi12.4, soi12.0) | C2 |
271 | 704.414.4 | Where used as a protective measure the requirements of SELV or PELV has not been met. Regulation 704.414.4 (soi12.5, soi12.0) | C2 |
272 | 704.537.2.2 | The requirements for Assemblies for Construction Sites (ACS) which comprises of a suitable device for the switching and isolation of the incoming supply having the facility to be locked off or inside a lockable enclosure also comprising of overcurrent protective device(s), fault current protection device(s) and if required, socket-outlet(s) has not been met. Regulation 704.537.2.2 (soi12.6, soi12.0) | C2 |
273 | 705.411.1 | Circuits supplying socket-outlet(s) up to and including 32 amps require additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn . Regulation 705.411.1 (soi13.1.1, soi13.0) | C2 |
274 | 705.411.1 | Circuits supplying socket(s) with a rated current exceeding 32 amps require additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 100mA. Regulation 705.411.1 (soi13.1.2, soi13.0) | C2 |
275 | 705.411.1 | All circuits not including circuits supplying socket-outlet(s) require additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 300mA. Regulation 705.411.1 (soi13.1.3, soi13.0) | C2 |
276 | 705.414.5 | Where used as a protective measure the requirements of SELV or PELV has not been met. Regulation 705.414.5 (soi13.2, soi13.0) | C2 |
277 | 705.415.2.1 | In locations intended for livestock additional protection by supplementary bonding connecting all exposed-conductive-parts to all extraneous-conductive-parts including where applicable metal grid(s) laid in the floor and any concrete reinforcement steel work is required. Regulation 705.415.2.1 (soi13.3, soi13.0) | C2 |
278 | 705.422 | Electrical heating appliances have been fixed or sited so as not to maintain an appropriate distance from livestock and/or combustible material for the protection against fire and/or burns. Regulation 705.422 (soi13.4, soi13.0) | C2 |
279 | 705.512.2 | Socket-outlet(s) require to be positioned where they are unlikely to come into contact with combustible material. Regulation 705.512.2 (soi13.5, soi13.0) | C2 |
280 | 705.512.2 | All electrical equipment requires a minimum degree of IP44 protection or placed in an enclosure having a rating of IP44. Regulation 705.512.2 (soi13.5, soi13.0) | C2 |
281 | 705.512.2 | Where there is risk to socket-outlets from external influences (>AD4 – greater than splashed water e.g hosed water, >AE3 or ingress of objects greater than 1.00mm or >AG1 or danger of mechanical impact greater than low severity) additional protection has not been provided. Regulation 705.512.2 (soi13.5, soi13.0) | C2 |
282 | 705.512.2 | Where corrosive substances are present e.g in dairies or cattle sheds electrical equipment and/or wiring systems require additional protection. Regulation 705.512.2 (soi13.5, soi13.0) | C2 |
283 | 705.513.2 | General items of electrical equipment are accessible to livestock. (Does not include equipment for the feeding or watering for livestock). Regulation 705.513.2 (soi13.6, soi13.0) | C2 |
284 | 705.513.2 | Electrical equipment and/or wiring systems intended for feeding and/or watering of livestock requires additional mechanical protection to minimize the risk of injury to livestock. Regulation 705.513.2 | C2 |
285 | 705.514.9 | Diagrams and documentation showing the location of all electrical equipment, routing of all concealed cables, single line distribution and locations of bonding connections is not available. Regulation 705.514.9 (soi13.7, soi13.0) | C3 |
286 | 705.522 | The wiring system has been installed so as to be accessible to livestock or not suitably protected against mechanical damage. Regulation 705.522 (soi13.8, soi13.0) | C2 |
287 | 705.522 | Overhead lines require insulating. Regulation 705.522 (soi13.8, soi13.0) | C1 |
288 | 705.522.16 | Where livestock is kept, conduit, trunking or cable ducting systems require a classification of AF4 (designed for the nature of substances) and be protected against corrosion - Class 2 (medium) for indoor use and Class 4 (high protection) for outdoor use. Regulation 705.522.16 (soi13.9, soi13.0) | C2 |
289 | 705.522.16 | Where the wiring system may be exposed to impact and mechanical damage from vehicles, agricultural machines etc. reinforced protection is required to a classification of AG3 (High severity of mechanical stress/impact). Regulation 705.522.16 (soi13.9, soi13.0) | C2 |
290 | 705.537.2 | A single isolation device is required for the electrical installation of each building or part of a building. Regulation 705.537.2 (soi13.10.1, soi13.0) | C2 |
291 | 705.537.2 | Isolation devices required to isolate all live conductors including the neutral conductor of circuits that are only used occasionally e.g during harvest time. Regulation 705.537.2 (soi13.10.2, soi13.0) | C2 |
292 | 705.537.2 | Isolation devices require to be clearly marked to show which part of the installation they control. Regulation 705.537.2 | C3 |
293 | 705.537.2 | Devices for isolation or switching or devices for emergency stopping or switching are accessible to or may be impeded by livestock. Regulation 705.537.2 (soi13.10.3, soi13.0) | C2 |
294 | 705.544.2 | Supplementary equipotential bonding conductors require protection against mechanical damage. Regulation 705.544.2 (soi13.11, soi13.0) | C3 |
295 | 705.544.2 | Supplementary equipotential bonding conductors are of the type suffering from electrolytic effects. Regulation 705.544.2 (soi13.11, soi13.0) | C3 |
296 | 705.544.2 | Supplementary equipotential bonding conductors suffering corrosion. Regulation 705.544.2 (soi13.11, soi13.0) | C3 |
297 | 705.533.1 | Socket-outlets type require compliance with BS EN 60309-1 or BS EN 60309-2 or where the rated current does not exceed 20 amps BS 1363 or BS 546. Regulation 705.533.1 (soi13.12, soi13.0) | C2 |
298 | 705.560.6 | Where high density livestock rearing is carried out an alternative or back-up secure source of supply is required for circuits controlling the supply of food, water, air and/or lighting where the normal supply is not ensured in the event of a power supply failure. Regulation 705.560.6 (soi13.13, soi13.0) | C2 |
299 | 705.560.6 | Where high density livestock rearing is carried out separate final circuits have not been provided for the supply of electrical equipment for the operation of ventilation and lighting. Regulation 705.560.6 (soi13.13, soi13.0) | C3 |
300 | 705.560.6 | Where high density livestock rearing is carried out discrimination of the main circuits supplying ventilation is required in the event of any short-circuit to earth or overcurrent. Regulation 705.560.6 (soi13.13, soi13.0) | C3 |
301 | 705.560.6 | Where high density livestock rearing is carried out an alternative or back-up secure source of supply is required for ventilation equipment or temperature and supply voltage monitoring devices which provide a visual or audible alarm signal that is easily observed which is operated independently from the normal supply. 705.560.6 (soi13.13, soi13.0) | C2 |
302 | 706.410.3.10 | In a conducting location with restricted movement, hand-held tools and/or item(s) of mobile equipment the requirement of a protective measure of either electrical separation or SELV has not been met. Regulation 706.410.3.10 (soi14.1, soi14.0) | C2 |
303 | 706.410.3.10 | In a conducting location with restricted movement, for handlamps, the requirement of SELV as a protective measure has not been met. Regulation 706.410.3.10 (soi14.1, soi14.0) | C2 |
304 | 706.410.3.10 | In a conducting location with restricted movement the supply to fixed equipment require the following protective measure of either: automatic disconnection of supply with supplementary bonding connecting all exposed-conductive-parts of fixed equipment and the conductive parts of the location or by use of Class II equipment having additional protection of the supply circuits by use of RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn having the RCD(s) outside of the location or electrical separation or SELV or PELV provided equipotential bonding is connecting the PELV system to all exposed-conductive-parts and extraneous conductive parts. Regulation 706.410.3.10 (soi14.1, soi14.0) | C2 |
305 | 706.413.1.2 | In a conducting location where the protective measure of electrical separation is employed, unless the source is part of a fixed installation within the conducting location as provided by item (iii) of Regulation 706.410.3.10 the unearthed source requires simple separation and be situated outside of the conducting location. Regulation 706.413.1.2 (soi14.2, soi14.0) | C2 |
306 | 706.410.3.10 | In a conducting location where the protective measure is afforded by the use of SELV or PELV the source is required to be situated outside of the conducting location unless the source is part of a fixed installation within the conducting location as provided by item (iii) of Regulation 706.410.3.10 (soi14.3, soi14.0) | C2 |
307 | 708.411.4 | The requirements of The Electrical Safety, Quality and Continuity Regulations 2002 (ESQCR) where it prohibits the connection of a PME facility to any metalwork in a leisure accommodation vehicle including a caravan has not been met. Regulation 708.411.4 (soi15.1, soi15.0) | C2 |
308 | 708512.2 | Electrical equipment situated outside is not suitable for external influences in terms of IP rating for one or more of the following: Presence of water AD4 (water splashes) IPX4, foreign solid bodies AE2 (small objects) IP3X or mechanical stress AG3 (high severity) IK08. Regulation 708512.2 (soi15.2, soi15.0) | C2 |
309 | 708.521.1.2 | All overhead conductors require to be insulated. Regulation 708.521.1.2 (soi15.3.1, soi15.0) | C1 |
310 | 708.521.2 | All poles and/or supports for overhead wiring require locating or protection against damage by vehicles. Regulation 708.521.2 (soi15.3.2, soi15.0) | C2 |
311 | 708.521.1.2 | All overhead conductors require to be at least 6 metres above the ground where subject to vehicle movement and 3.5 metres in all other areas. Regulation 708.521.1.2 (soi15.3.3, soi15.0) | C2 |
312 | 708.530.3 | The electricity supply equipment is required to be not mounted more than 20 metres away from the connection to the caravan, leisure accommodation vehicle or tent. Regulation 708.530.3 (soi15.4, soi15.0) | C3 |
313 | 708.553.1.8 | Where a socket-outlet and it's enclosure forms part of the pitch supply equipment it is required to comply with BS EN 60309-2 and have a degree of protection of at least IP44. Regulation 708.553.1.8 (soi15.5.1, soi15.0) | C2 |
314 | 708.553.1.9 | All socket-outlets of their lowest point require to be mounted at a height of between 0.5 metres to 1.5 metres above the ground. Regulation 708.553.1.9 (soi15.5.2, soi15.0) | C3 |
315 | 708.553.1.10 | All socket-outlets require to be rated at not less than 16 amps. Regulation 708.553.1.10 (soi15.5.3, soi15.0) | C3 |
316 | 708.553.1.11 | Each pitch requires at least one socket-outlet. Regulation 708.553.1.11 (soi15.5.4, soi15.0) | C3 |
317 | 708.553.1.12 | Each socket-outlet requires an individual overcurrent protective device(s). Regulation 708.553.1.12 (soi15.5.5, soi15.0) | C3 |
318 | 708.553.1.13 | Each socket-outlet requires individual protection by RCD(s) disconnecting all poles including the neutral having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn. Regulation 708.553.1.13 (soi15.5.6, soi15.0) | C2 |
319 | 708.553.1.14 | The requirement that the protective conductors of socket-outlets are not connected to PME earthing system has not been met. Regulation 708.553.1.14 (soi15.5.7, soi15.0) | C2 |
320 | 709.411.4 | The requirements of The Electrical Safety, Quality and Continuity Regulations 2002 (ESQCR) where it prohibits the connection of a PME facility to any metalwork in a boat has not been met. Regulation 709.411.4 (soi16.1, soi16.0) | C2 |
321 | 709.512.2.1.1 | The requirement for electrical equipment installed on or above a jetty, wharf or pontoon in relation to the external influences that, in the opinion of the inspector with regard to the risk of water splashes (AD4) IPX4 or water jets (AD5) IPX5 or water waves (AD6) IPX6 has not been met. Regulation 709.512.2.1.1 (soi16.2, soi16.0) | C2 |
322 | 709.512.2.1.2 | Electrical equipment installed on or above a jetty, wharf or pontoon requires a degree of protection of at least IP3X to protect against the ingress of small objects (AE2). Regulation 709.512.2.1.2 (soi16.2, soi16.0) | C3 |
323 | 709.512.2.1.3 | Electrical equipment installed on or above a jetty, wharf or pontoon requires to be suitable for atmospheric corrosive (sea salt spray) or polluting substances and/or exposed to exhaust fumes (hydrocarbons). Regulation 709.512.2.1.3 (soi16.2, soi16.0) | C3 |
324 | 709.512.2.1.4 | Electrical equipment installed on or above a jetty, wharf or pontoon requires protection against mechanical damage (impact of medium severity AG2) Regulation 709.512.2.1.4 (soi16.2, soi16.0) | C2 |
325 | 709.521.1.5 | The installation of one or more of the following wiring systems on or above a jetty, wharf or pontoon: cables in free air supported by a catenary wire, non-sheathed cables in a cable management system e.g conduit, trunking etc., cables with aluminium conductors or mineral insulated cables should not be used. Regulation 709.521.1.5 (soi16.3, soi16.0) | C2 |
326 | 709.521.1.6 | Cables require selecting and/or installed to prevent mechanical damage due to tidal or movement of pontoons, boats or other floating structures. Regulation 709.521.1.6 (soi16.3, soi16.0) | C2 |
327 | 709.521.1.6 | Cable management system(s) suffering ingress of water, requires installation of drainage holes. Regulation 709.521.1.6 (soi16.3, soi16.0) | C2 |
328 | 709.531.2 | Each socket-outlet requires additional protection by RCD(s) disconnecting all poles including the neutral having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn. Regulation 709.531.2 (soi16.4, soi16.0) | C2 |
329 | 709.553 | Each socket-outlet requires an individual overcurrent protective device(s). Regulation 709.553 (soi16.5, soi16.0) | C3 |
330 | 709.531.2 | A final circuit for a fixed connection to a houseboat requires individual protection by an RCD disconnecting all poles including the neutral having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn. Regulation 709.531.2 (soi16.6, soi16.0) | C2 |
331 | 709.533 | A final circuit for a fixed connection to a houseboat requires individual overload protection device(s). Regulation 709.533 (soi16.7, soi16.0) | C3 |
332 | 709.537.2.1.1 | A means of isolation is required in each distribution cabinet limiting each isolation switch for a maximum of four socket-outlets. Regulation 709.537.2.1.1 (soi16.8, soi16.0) | C2 |
333 | 709.553.1.9 | All socket-outlets require a protection of IP44 or installed in an enclosure affording the equivalent protection. Regulation 709.553.1.9 (soi16.9, soi16.0) | C2 |
334 | 709.553.1.9 | All socket-outlets where subject to jetted water (hoses) require protection to be at least IPX5. Regulation 709.553.1.9 (soi16.9, soi16.0) | C2 |
335 | 709.553.1.9 | All socket-outlets where subject to waves require protection to be at least IPX6. Regulation 709.553.1.9 (soi16.9, soi16.0) | C2 |
336 | 709.553.1.9 | 10 & 11 ,'Socket-outlets need to be sited as close as possible to each berth having one socket for each berth to avoid tripping hazards due to long extension cords. Regulations 709.553.1.9, 10 & 11 (soi16.10, soi16.0) | C3 |
337 | 709.553.1.12 | Single phase socket-outlets with a rated voltage of 200 to 250 volts require to have a current rating of 16amps. Regulation 709.553.1.12 (soi16.11, soi16.0) | C3 |
338 | 709.553.1.13 | Socket-outlets not sited on floating pontoons or walkways require to sited at least one metre above the highest water level. Regulation 709.553.1.13 (soi16.12, soi16.0) | C2 |
339 | 709.553.1.13 | Socket-outlets positioned on floating pontoons or walkways where sited at a reduced height of a minimum 300mm above the highest water level requires appropriate protection for risk of splashing. Regulation 709.553.1.13 (soi16.12, soi16.0) | C2 |
340 | 709.553.1.14 | A socket-outlet protective conductor has been connected to a PME earthing facility. Regulation 709.553.1.14 (soi16.13, soi16.0) | C2 |
341 | - | Warning notices being durable and easily legible for “Instructions for Electricity Supply” require mounting in the appropriate locations. Figure 709.3 (soi16.14, soi16.0) | C3 |
342 | 711.32 | Where temporary electrical installations have been installed protection against external influences such as water and/or mechanical stresses are required. Regulation 711.32 (soi18.1, soi18.0) | C2 |
343 | 711.410.3.4 | Cable(s) supplying temporary structure(s) require protection at the origin by an RCD not exceeding 300mA and having a time delay device for discrimination with RCD(s) protecting final circuits. Regulation 711.410.3.4 (soi18.2, soi18.0) | C2 |
344 | 711.411.3.1.2 | All extraneous structural parts that are accessible from within the stand, vehicle, wagon, caravan or container require connecting via the main protective conductors to the main earthing terminal within the unit. Regulation 711.411.3.1.2 (soi18.3, soi18.0) | C2 |
345 | 711.411.3.3 | All socket-outlets not exceeding 32amps require additional protection by an RCD having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 IΔn Regulation 711.411.3.3 (soi18.4, soi18.0) | C2 |
346 | 711.411.3.3 | All final circuits except for emergency lighting require additional protection by an RCD not exceeding 30mA. Regulation 711.411.3.3 (soi18.4, soi18.0) | C2 |
347 | 711.411.4 | A PME earthing system has been used where suitability and effectiveness has not been confirmed before the connection has been made and/or the installation is not under the supervision of a skilled or instructed person. Regulation 711.411.4 (soi18.5, soi18.0) | C2 |
348 | 711.414.4.5 | Where used as a protective measure for electrical equipment the requirements of SELV or PELV has not been met having lack of basic insulation or barriers or enclosures affording protection of at least IPXXD or IP4X. Regulation 711.414.4.5 (soi18.6, soi18.0) | C2 |
349 | 711.422.4.2 | Equipment that generate high surface temperatures e.g. lamps, spotlights, heaters etc. require suitable guards and installed and located with the relevant standard. Regulation 711.422.4.2 (soi18.7, soi18.0) | C2 |
350 | 711.422.4.2 | Showcases and/or signs require to be constructed having adequate heat-resistance, mechanical strength, electrical insulation and ventilation taking into account heat generation and the combustibility of exhibits. Regulation 711.422.4.2 (soi18.7, soi18.0) | C2 |
351 | 711.422.4.2 | Stand(s) having a concentration of electrical equipment that is liable to generate excessive heat requires adequate ventilation. 711.422.4.2 (soi18.7, soi18.0) | C2 |
352 | 711.51 | Switchgear and/or control-gear not intended to be used by ordinary persons require enclosing in a cabinet that can only be opened by a key or use of a tool. Regulation 711.51 (soi18.8, soi18.0) | C2 |
353 | 711.52 | Where the public have access, armoured cables or mechanical protection for flexible cables is required. Regulation 711.52 (soi18.9, soi18.0) | C2 |
354 | 711.521 | This installation not having a fire alarm system installed requires a wiring system that is either flame retardant and having low smoke properties or where single core or multi-core unarmoured cables are used, being installed in enclosed metallic or non-metallic conduit or trunking providing the required fire protection and a degree of at least IP4X protection. Regulation 711.521 (soi18.10, soi18.0) | C2 |
355 | 711.526.1 | Joints of electrical connections require being made in appropriate enclosure(s) having a degree of protection of at least IPXXD or IP4X. Regulation 711.526.1 (soi18.11, soi18.0) | C2 |
356 | 711.526.1 | Suitable cable anchorages are required where strain can be placed upon electrical terminals. Regulation 711.526.1 (soi18.11, soi18.0) | C2 |
357 | 711.537.2.3 | A readily accessible and identifiable means of isolation is required for every separate temporary structure such as vehicle, stand or unit. The means of isolation requires selecting and erecting in accordance with Regulation 537.2. Regulation 711.537.2.3 (soi18.12, soi18.0) | C2 |
358 | 711.537.2.3 | A readily accessible and identifiable means of isolation is required for distribution circuit(s) supplying outdoor installation(s). The means of isolation requires selecting and erecting in accordance with Regulation 537.2. Regulation 711.537.2.3 (soi18.12, soi18.0) | C2 |
359 | 711.55.1.5 | Electrical equipment requires to be sited, fixed and protected against ignition of material caused by the danger of focusing or concentration of heat. Regulation 711.55.1.5 (soi18.13, soi18.0) | C2 |
360 | 711.55.4.1 | Readily accessible isolation is required for electric motors where they might give rise to a hazard. Regulation 711.55.4.1 (soi18.14, soi18.0) | C2 |
361 | 711.55.6 | ELV transformer(s) and electronic converters require mounting out of arm's reach. Regulation 711.55.6 (soi18.15, soi18.0) | C2 |
362 | 711.55.6 | ELV transformer(s) and electronic converters require adequate ventilation. Regulation 711.55.6 (soi18.15, soi18.0) | C2 |
363 | 711.55.6 | ELV transformer(s) and electronic converters require a manual reset protective device (e.g. mcb) installed in the secondary circuit. Regulation 711.55.6 (soi18.15, soi18.0) | C2 |
364 | 711.55.7 | An adequate number of sockets have not been provided. Regulation 711.55.7 (soi18.16, soi18.0) | C2 |
365 | 711.55.7 | Where floor sockets have been used additional protection from accidental ingress of water has not been provided. Regulation 711.55.7 (soi18.16, soi18.0) | C2 |
366 | 711.55.7 | Floor sockets require additional protection to withstand the expected traffic load. Regulation 711.55.7 (soi18.16, soi18.0) | C2 |
367 | 711.559.4.3 | Non-compatible cable has been used where insulation piercing lampholders are fitted. Regulation 711.559.4.3 (soi18.17, soi18.0) | C2 |
368 | 711.559.4.3 | Where insulation piercing lampholders are being used they are required to be of the non-removable type once fitted. Regulation 711.559.4.3 (soi18.17, soi18.0) | C3 |
369 | 711.559.4.4.1 | Electrical discharge lamp equipment incorporating signs, tubes or lamps with an operating voltage higher than 230/400 volts requires installing out of arm's reach or adequately protected against risk of injury to persons. Regulation 711.559.4.4.1 (soi18.18.1, soi18.0) | C2 |
370 | 711.559.4.4.2 | Fascia or stand material at risk of fire from ignition due to hot parts behind signs, tubes or lamps of electrical equipment incorporating discharge lamp installation(s) with an operating voltage higher than 230/400 volts requires material to be non-ignitable. Regulation 711.559.4.4.2 (soi18.18.2, soi18.0) | C2 |
371 | 711.559.4.4.3 | A separate circuit is required for the supply of signs, lamps or exhibits of electrical equipment incorporating discharge lamp installation(s) with an operating voltage higher than 230/400 volts. Regulation 711.559.4.4.3 (soi18.18.3, soi18.0) | C3 |
372 | 711.559.4.4.3 | A circuit supplying supply of signs, lamps or exhibits of electrical equipment incorporating discharge lamp installation(s) with an operating voltage higher than 230/400 volts requires controlling by an emergency switch which is easily identifiable and clearly labelled. Regulation 711.559.4.4.3 (soi18.18.3, soi18.0) | C2 |
373 | 711.559.5 | Luminaires mounted below arm's reach (2.5metres) from the floor or otherwise accessible require adequate fixing and sited or guarded to prevent injury to persons or risk of fire by ignition of materials. Regulation 711.559.5 (soi18.19, soi18.0) | C2 |
374 | 711.559.5 | Luminaires mounted below arm's reach (2.5metres) from the floor or otherwise accessible require having access to the fixed light source by the removal of a barrier or an enclosure by the use of a tool. Regulation 711.559.5 (soi18.19, soi18.0) | C2 |
375 | 712.312.2 | At least simple separation is required between the a.c. side and d.c. side where earthing of one of the live conductors on the d.c. side has been carried out. Regulation 712.312.2 | C2 |
376 | 712.411.3.2.1.1 | On the a.c side the PV supply cable has not been connected to the supply side of the protective device of circuits supplying current-using equipment. Regulation 712.411.3.2.1.1 (soi19.1.1, soi19.0) | C2 |
377 | 712.411.3.2.1.2 | RCD protection required for the PV power supply system where at least simple separation between the a.c side and d.c side has not been provided. Regulation 712.411.3.2.1.2 (soi19.1.2, soi19.0) | C2 |
378 | 712.412 | Class II or equivalent insulation has not been used as the preferable protective measure on the d.c side. Regulation 712.412 (soi19.2, soi19.0) | C3 |
379 | 712.433.1 | Overload protection has not been provided or is too large where the continuous current carrying capacity of the PV string and/or PV array cables is less than 1.25 times Isc STC. Regulation 712.433.1 (soi19.3, soi19.0) | C2 |
380 | 712.433.2 | Overload protection has not been provided or is too large where the continuous current carrying capacity of the PV main cable is less than 1.25 times Isc STC of the PV generator. Regulation 712.433.2 (soi19.3, soi19.0) | C2 |
381 | 712.444.4.4 | Where there is risk of voltages induced by lightning wiring loops have not been kept as small as possible. Regulation 712.444.4.4 (soi19.5, soi19.0) | C2 |
382 | 712.512.1.1 | Electrical equipment provided and installed on the d.c side is not suitable for direct voltage and direct current. Regulation 712.512.1.1 (soi19.6, soi19.0) | C2 |
383 | 712.512.1.1 | The maximum allowed operating voltage of the PV modules (Uoc STC of the PV strings) and the PV convertor (whichever is lower) is being exceeded where PV modules have been connected in series. Regulation 712.512.1.1 (soi19.7, soi19.0) | C2 |
384 | 712.513.1 | Equipment has not been erected to enable maintenance work to be carried out safely. Regulation 712.513.1 (soi19.8, soi19.0) | C3 |
385 | 712.522.8.3 | PV string cables have not been selected and/or erected to minimize the risk of earth faults and/or short-circuits. Regulation 712.522.8.3 (soi19.9, soi19.0) | C3 |
386 | 712.522.8.3 | PV array cables have not been selected and or erected to minimize the risk of earth faults and/or short-circuits. Regulation 712.522.8.3 (soi19.9, soi19.0) | C3 |
387 | 712.522.8.3 | PV d.c main cables have not been selected and or erected to minimize the risk of earth faults and/or short-circuits. Regulation 712.522.8.3 (soi19.9, soi19.0) | C3 |
388 | 712.522.8.3 | PV string and/or array and/or d.c main cables have not been selected and or erected to minimize the risk of earth faults and/or short-circuits. Regulation 712.522.8.3 (soi19.9, soi19.0) | C3 |
389 | 712.522.8.3 | Wiring system(s) are unsuitable for external influences such as wind, ice formation, temperature and solar radiation. Regulation 712.522.8.3 (soi19.10, soi19.0) | C2 |
390 | 712.537.2.1.1 | Means of isolation for maintenance purposes required for isolating the PV convertor from the d.c side and the a.c side. Regulation 712.537.2.1.1 (soi19.11, soi19.0) | C2 |
391 | 712.537.2.2.5 | A switch-disconnector is required on the d.c side of the PV convertor. Regulation 712.537.2.2.5 (soi19.12, soi19.0) | C2 |
392 | 712.537.2.2.5.1 | A warning label is required on PV generator and PV array junction boxes indicating that parts may still be live after isolation from the PV convertor. Regulation 712.537.2.2.5.1 (soi19.13, soi19.0) | C3 |
393 | 712.54 | Where protective bonding conductors have been installed they are required to be parallel to and in as close contact as possible to d.c and a.c cables and accessories. Regulation 712.54 | C3 |
394 | 717.313 | The requirements of a connection to a low voltage generating set in accordance with Section 551 and Figures 717.1 and 717.2 have not been met. Regulation 717.313 (soi20.1.1, soi20.0) | C2 |
395 | 717.313 | The requirements of a connection to a fixed electrical installation having the protective measure of TT or TN and Figure 717.3 are not effective and therefore not met. Regulation 717.313 (soi20.1.2, soi20.0) | C2 |
396 | 717.313 | The requirements of a connection from a fixed installation through means provided by simple separation in accordance with Section 413 and Figures 717.4, 717.6 and 717.7 have not been met. Regulation 717.313 (soi20.1.3, soi20.0) | C2 |
397 | 717.411.1 | An RCD for the automatic disconnection of the supply is required. Regulation 717.411.1 (soi20.2, soi20.0) | C2 |
398 | 717.411.3.1.2 | All accessible conductive parts (e.g chassis) require connecting through the main protective bonding conductor(s) to the main earthing terminal within the unit. Regulation 717.411.3.1.2 (soi20.3, soi20.0) | C2 |
399 | 717.411.3.1.2 | Protective bonding conductors are required to be finely stranded for protection against vibration. Regulation 717.411.3.1.2 (soi20.3, soi20.0) | C3 |
400 | 717.411.4 | A PME earthing system has been used where suitability and effectiveness has not been confirmed before the connection has been made and/or the installation is not under the supervision of a skilled or instructed person. Regulation 717.411.4 (soi20.4, soi20.0) | C2 |
401 | 717.411.6.2 | An IT earthing system is being used within the unit, the requirements of a means of protection by the use of an isolating transformer or a low voltage generating set as per Figure 717.7 has not been met. Regulation 717.411.6.2 (soi20.5.1, soi20.0) | C2 |
402 | 717.411.6.2 | An IT earthing system is being used within the unit, the requirements of a means of protection by the use of a transformer providing simple separation with an RCD and an earth electrode have not been met. Regulation 717.411.6.2 (soi20.5.2, soi20.0) | C2 |
403 | 717.415.1 | Other than socket-outlet(s) protected by SELV or PELV or electrical separation all socket-outlets supplied at low voltage intended to supply current-using equipment outside the unit require additional protection by RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn . Regulation 717.415.1 (soi20.6, soi20.0) | C2 |
404 | 717.514 | Warning notices being durable and easily legible require mounting adjacent to each supply inlet conductor stating i) The type of supplies which may be connected to the unit ii) The voltage rating of the unit iii) The number of supplies, phases and their configuration iv) The on-board earthing arrangement v) The maximum power requirement of the unit as per Figure 709.3. Regulation 717.514 (soi20.7, soi20.0) | C3 |
405 | 717.52.1 | Cable(s) connecting the unit to the supply require to be flexible and in accordance with H07RN-F (BS 7919) or of an equivalent design. Regulation 717.52.1 (soi20.8, soi20.0) | C2 |
406 | 717.52.1 | Cable(s) entering the unit require protection by an insulating inlet to protect against damage to the insulation of the cable or fault which might energize any exposed-conductive-parts of the unit. Regulation 717.52.1 (soi20.8, soi20.0) | C2 |
407 | 717.52.2(i) | Where unsheathed flexible cables are used within the unit, the cables require protection by being installed in either conduit, trunking or ducting for mechanical protection. Regulation 717.52.2(i) (soi20.9.1, soi20.0) | C2 |
408 | 717.52.2(ii) | Where sheathed flexible cables are used within the unit, the cables require precautionary measures to protect against mechanical damage likely to occur from sharp edged parts or abrasion. Regulation 717.52.2(ii) (soi20.9.2, soi20.0) | C2 |
409 | 717.528.3.4 | Electrical equipment and wiring other than ELV equipment and ELV wiring for the gas control supply shall not be stored in gas cylinder storage compartment(s). Regulation 717.528.3.4 (soi20.10.1, soi20.0) | C2 |
410 | 717.528.3.4 | There is a risk of ignition within the gas cylinder compartment due to the construction and/or method of installation of the ELV equipment and/or ELV wiring serving the operation of the gas cylinder Regulation 717.528.3.4 (soi20.10.2, soi20.0) | C2 |
411 | 717.528.3.4 | Where cables have to run through a gas cylinder compartment they require protection against mechanical damage by use of conduit or an appropriate ducting system. Regulation 717.528.3.4 (soi20.10.3, soi20.0) | C2 |
412 | 717.528.3.4 | Where conduit or a ducting system has been installed in a gas cylinder compartment the conduit or ducting requires to be able to withstand an impact equivalent to AG3 (high severity – reinforced protection). Regulation 717.528.3.4 (soi20.10.3, soi20.0) | C2 |
413 | 717.55.1 | Connecting devices that are mounted, accessed, used outside the unit or used to connect the unit to the supply or other equipment require enclosure(s) of insulating material having a degree of protection of at least IP44 when connected and at least IP55 when not connected. Regulation 717.55.1 (soi20.11, soi20.0) | C2 |
414 | 717.55.3 | Generating sets producing low voltage (not SELV or PELV) mounted in the unit require to have automatic switching off in case of an accident or isolation by means of an easily accessible emergency switch. Regulation 717.55.3 (soi20.12, soi20.0) | C2 |
415 | 721.410.3.3.1 | Where a portion of a caravan is operating at extra-low voltage (ELV) SELV and PELV circuits require basic insulation between live parts and other SELV or PELV circuits and protective separation from live parts at low voltage by double or reinforced insulation or by basic insulation and protective screening for the highest voltage that is present as per Regulation 414.1. Regulation 721.410.3.3.1 (soi21.0) | C2 |
416 | 721.410.3.3.1 | Luminaire supporting coupler(s) on a SELV or PELV system have been used where they are compatible with other plugs on other systems (low voltage) as per Regulation 414.4.3. Regulation 721.410.3.3.1 (soi21.1, soi21.0) | C2 |
417 | 721.410.3.3.1 | Socket-outlet(s) on a SELV or PELV system have been used where they are compatible with other plugs on other systems (low voltage). as per Regulation 414.4.3. Regulation 721.410.3.3.1 (soi21.1, soi21.0) | C2 |
418 | 721.410.3.3.2 | The protective measure of electrical separation as per Section 413 is not permitted except for shaver socket-outlets. Regulation 721.410.3.3.2 (soi21.2, soi21.0) | C2 |
419 | 721.411.1 | The protective measure by automatic disconnection of supply is being used (Section 411). RCD protection not exceeding 30mA is required with the wiring system having a circuit protective conductor connected to i) the protective contact of the inlet. ii) the exposed-conductive-parts of the electrical equipment and iii) the protective contacts of the socket-outlets. Regulation 721.411.1 (soi21.3, soi21.0) | C2 |
420 | 721.411.3.1.2 | Structural metallic parts that are accessible from within the caravan require connecting through main bonding conductors to the main earthing terminal within the caravan. Regulation 721.411.3.1.2 (soi21.4, soi21.0) | C2 |
421 | 721.43.1 | All final circuits require individual protection by an overcurrent device which disconnects all live conductors. Regulation 721.43.1 (soi21.5, soi21.0) | C2 |
422 | 721514.1 | Instructions for use is required so that the caravan can be used safely comprising of i) a description of the installation. ii) a description of the RCD(s) and the use of the test button(s). iii) a description of the function of the main isolating switch. iv) a text permanently fixed near the main isolating switch inside the caravan “Instructions for electricity supply” as per Figure 721 . Regulation 721514.1 (soi21.6, soi21.0) | C3 |
423 | 721.521.2 | The requirements for the only types of wiring which are i) Insulated single-core class 5 flexible cables having multiple fine stranded conductors in non-metallic conduit. ii) Insulated single-core class 2 flexible cables having stranded conductors (minimum of 7 strands) in non-metallic conduit. iii) Sheathed flexible cables have not been met. Regulation 721.521.2 (soi21.7, soi21.0) | C2 |
424 | 721.522.7.1 | As the wiring will be subject to vibration, all wiring is required to be protected by either location or enhanced mechanical protection to against mechanical damage, wiring passing through metalwork requires protection by means of bushes or grommets securely fixed into position. Regulation 721.522.7.1 (soi21.8, soi21.0) | C2 |
425 | 721.522.7.1 | Wiring passing through metalwork requires protection by means of bushes or grommets securely fixed into position as the wiring will be subject to vibration. Regulation 721.522.7.1 (soi21.8, soi21.0) | C2 |
426 | 721.522.7.1 | As the wiring will be subject to vibration protection is required to avoid mechanical damage to cables from sharp edges or abrasive parts. Regulation 721.522.7.1 (soi21.8, soi21.0) | C2 |
427 | 721.522.8.1.3 | Where cables are not installed within rigid conduit all cables and flexible conduit requires supporting at intervals not exceeding 0.4 of a metre for vertical runs and 0.25 of a metre for horizontal runs. Regulation 721.522.8.1.3 (soi21.9, soi21.0) | C3 |
428 | 721.524.1 | All conductors require a minimum cross-sectional area of not less than 1.5mm2. Regulation 721.524.1 (soi21.10, soi21.0) | C3 |
429 | 721.528.1 | Cables of LV systems require to be run separately from cables of extra-low voltage systems in so far as reasonably practicable that there is no physical contact between cables of LV and that of extra-low systems. Regulation 721.528.1 (soi21.11, soi21.0) | C2 |
430 | 721.528.3.4 | There is a risk of ignition within the gas cylinder compartment due to the construction and/or method of installation of the ELV equipment and/or ELV wiring serving the operation of the gas cylinder Regulation 721.528.3.4 (soi21.12.1, soi21.0) | C2 |
431 | 721.528.3.4 | Where cables have to run through a gas cylinder compartment they require protection against mechanical damage by use of conduit or an appropriate ducting system. Regulation 721.528.3.4 (soi21.12.2, soi21.0) | C2 |
432 | 721.528.3.4 | Where conduit or a ducting system has been installed in a gas cylinder compartment the conduit or ducting requires to be able to withstand an impact equivalent to AG3 (high severity – reinforced protection). Regulation 721.528.3.4 (soi21.12.3, soi21.0) | C2 |
433 | 721.537.2.1.1 | A main disconnector is required which disconnects all live conductors and is placed within easy access in the caravan. Regulation 721.537.2.1.1 (soi21.13, soi21.0) | C2 |
434 | 721.537.2.1.1 | The main disconnector within the caravan is not within easy access. Regulation 721.537.2.1.1 (soi21.13, soi21.0) | C3 |
435 | 721.543.2.3 | All circuit protective conductors are required to be incorporated within a multicore cable or in a conduit together with the live conductors. Regulation 721.543.2.3 (soi21.14, soi21.0) | C3 |
436 | 721.55.1 | The electrical inlet is required to be an appliance inlet complying with BS EN 60309-1 or if interchangeability is required to comply with BS EN 60309-2. Regulation 721.55.1 (soi21.15, soi21.0) | C2 |
437 | 721.55.1 | The electrical inlet should not be installed at 1.8 metres or more above the ground level on which the caravan sits. Regulation 721.55.1 (soi21.15, soi21.0) | C3 |
438 | 721.55.1 | The electrical inlet on the caravan has not been installed in a readily accessible position. Regulation 721.55.1 (soi21.15, soi21.0) | C3 |
439 | 721.55.1 | The electrical inlet requires a minimum degree of IP44 protection with or without a connector engaged. Regulation 721.55.1 (soi21.15, soi21.0) | C2 |
440 | 721.55.1 | The electrical inlet protrudes significantly beyond the body of the caravan, therefore at risk of mechanical damage . Regulation 721.55.1 (soi21.15, soi21.0) | C3 |
441 | 721.55.2.1 | Other than socket-outlets supplied by an individual winding of an isolating transformer all low voltage socket-outlets require an earth contact. Regulation 721.55.2.1 (soi21.16, soi21.0) | C2 |
442 | 721.55.2.2 | All socket-outlets supplied at extra-low voltage requires it's voltage to be visibly marked. Regulation 721.55.2.2 (soi21.17, soi21.0) | C3 |
443 | 721.55.2.3 | Accessory(s) exposed to moisture require to be constructed or enclosed having a degree of protection of not less than IP44. Regulation 721.55.2.3 (soi21.18, soi21.0) | C2 |
444 | 721.55.2.4 | Luminaires are required to be fixed directly to the structure or lining of the caravan. Regulation 721.55.2.4 (soi21.19, soi21.0) | C3 |
445 | 721.55.2.4 | Where luminaires are fixed directly to the structure or lining of the caravan, where applicable provision is required for a pendant luminaire to be secure to prevent damage when the caravan is in motion. Regulation 721.55.2.4 (soi21.19, soi21.0) | C2 |
446 | 721.55.2.4 | Where accessories have been used for the suspension of pendant luminaires, they are not suitable for the mass suspended and forces produced with vehicle movement. Regulation 721.55.2.4 (soi21.20, soi21.0) | C2 |
447 | 721.55.2.6 | The means of connecting the caravan to a caravan pitch socket-outlet requires a plug complying with BS EN 60309-2. Regulation 721.55.2.6 (soi21.21, soi21.0) | C2 |
448 | 721.55.2.6 | The means of connecting the caravan to a caravan pitch socket-outlet requires a cable of a harmonized code designation H05RN-F (BS 7919) or equivalent. Regulation 721.55.2.6 (soi21.21, soi21.0) | C2 |
449 | 721.55.2.6 | The flexible cable connecting the caravan to a caravan pitch socket-outlet requires to be between 23 and 27 metres long. Regulation 721.55.2.6 (soi21.21, soi21.0) | C3 |
450 | 721.55.2.6 | The flexible cable connecting the caravan to a caravan pitch socket-outlet requires to have a protective conductor incorporated within the cable. Regulation 721.55.2.6 (soi21.21, soi21.0) | C2 |
451 | 721.55.2.6 | The flexible cable connecting the caravan to a caravan pitch socket-outlet requires to have the conductors identifiable in accordance with Table 51. Regulation 721.55.2.6 (soi21.21, soi21.0) | C3 |
452 | 721.55.2.6 | The flexible cable connecting the caravan to a caravan pitch socket-outlet requires to have a cross-sectional area in accordance with Table 721. Regulation 721.55.2.6 (soi21.21, soi21.0) | C2 |
453 | 729.3 | Restricted access areas require clearly and visibly marked using appropriate signs. Regulation 729.3 (soi22.1, soi22.0) | C3 |
454 | 729.3 | Restricted access areas nor secure – access to unauthorised persons. Regulation 729.3 (soi22.1, soi22.0) | C2 |
455 | 729.3 | Restricted access areas doors provided for closed restricted access do not allow easy evacuation without the use of a key, tool or any other device not being part of the opening mechanism. Regulation 729.3 (soi22.1, soi22.0) | C3 |
456 | 729.513.2 | The width of the gangways and access areas are not adequate for work, operational access, emergency access, emergency evacuation and for the transport of equipment. Regulation 729.513.2 (soi22.2, soi22.0) | C3 |
457 | - | For easy evacuation compliance with Figures A729.1 i) where the doors of any equipment inside the location shall close in the direction of the evacuation route and A729.2 ii) gangways shall permit at least a 90 degree opening of equipment doors or hinged panels iii) where doors of equipment when opened are in a fixed position or circuit-breakers have been withdrawn fully (extracted position) for maintenance a minimum distance of 500mm is required between the enclosure door edge or circuit-breaker edge and the opposite limitation of the gangway such as a wall or other equipment have not been met. Annex A729 (soi22.3, soi22.0) | C3 |
458 | 729.513.2.1 | Where basic protection is provided by barriers or enclosures in accordance with Chapter 41 the minimum dimensions do not comply with Figure 729.1 where i) Gangway width including between barriers or enclosures and switch handles or circuit breakers in the most onerous position and barriers or enclosures or switch handles or circuit breakers in the most onerous position and the wall the minimum width is 700mm or ii) Gangway width between barriers or enclosures or other barriers or enclosures and the wall the minimum width is 700mm or iii) The height of a gangway to the barrier or enclosure above the floor is a minimum of 2000mm or iv) Where live parts are placed out of reach as per Regulation 417.3 the minimum distance from the floor is 2500mm. Regulation 729.513.2.1 (soi22.4, soi22.0) | C2 |
459 | 729.513.2.2 | Where the protective measure of obstacles is used in accordance with Section 417 and is subject to the control or supervision of skilled persons the minimum dimensions do not comply with Figure 729.2 where i) Gangway width including between obstacles and switch handles or circuit breakers in the most onerous position and obstacles or switch handles or circuit breakers in the most onerous position and the wall the minimum width is 700mm or ii) Gangway width between obstacles or other obstacles and the wall the minimum width is 700mm or iii) The height of a gangway to obstacles, barrier or enclosure above the floor is a minimum of 2000mm or iv) Where live parts are placed out of reach as per Regulation 417.3 the minimum distance from the floor is 2500mm. Regulation 729.513.2.2 (soi22.5, soi22.0) | C2 |
460 | 729.513.2.3 | Gangways longer than 10 metres require means of access from both ends complying with Figure 729.3 and having the doors opening outwards with minimum dimensions of 700mm width and a height of 2000mm. Regulation 729.513.2.3 (soi22.6.1, soi22.0) | C3 |
461 | 729.513.2.3 | Closed restricted access areas with a length exceeding 20 metres require accessibility by doors at both ends complying with Figure 729.3. and having the doors opening outwards with minimum dimensions of 700mm width and a height of 2000mm. Regulation 729.513.2.3 (soi22.6.2, soi22.0) | C3 |
462 | 740.313.3 | The requirement where irrespective of the number of supplies, there is no interconnection of the line and neutral conductors from different sources downstream of the origin of the temporary electrical installation has not been met. Regulation 740.313.3 (soi23.1, soi23.0) | C2 |
463 | 740.410.3 | Temporary electrical installations require an automatic disconnection of supply provided by a RCD not exceeding 300 mA. and is a time delay type where required to discriminate with downstream RCDs protecting final circuits. Regulation 740.410.3 (soi23.2, soi23.0) | C2 |
464 | 740.411.4.1 | A PME earthing facility has been used for an installation falling within this scope. Regulation 740.411.4.1 (soi23.3, soi23.0) | C2 |
465 | 740.411.4.1 | The requirements of The Electrical Safety, Quality and Continuity Regulations 2002 (ESQCR) where it prohibits the connection of a PME facility to any metalwork in a caravan or similar construction has not been met. Regulation 740.411.4.1 (soi23.3, soi23.0) | C2 |
466 | 740.415.1 | Except for circuits protected by SELV, PELV or electrical separation and lighting circuits not supplied by socket-outlets, all other circuits for lighting, socket-outlets rated up to 32A and mobile equipment connected by means of a flexible cable with a current capacity up to 32A require additional protection by means of RCDs not exceeding 30mA. Regulation 740.415.1 (soi23.4, soi23.0) | C2 |
467 | 705.415.2.1 | In locations intended for livestock additional protection by supplementary bonding connecting all exposed-conductive-parts to all extraneous-conductive-parts is required. Regulation 705.415.2.1 (soi13.3, soi13.0) | C2 |
468 | 740.422.3.7 | Motors which are automatically or remotely controlled and which are not continuously supervised require manually reset protective devices for protection against excessive temperatures. Regulation 740.422.3.7 (soi23.6, soi23.0) | C2 |
469 | 740.51 | Switchgear and/or control-gear not intended to be used by ordinary persons require enclosing in a cabinet that can only be opened by a key or use of a tool. Regulation 740.51 (soi23.7, soi23.0) | C2 |
470 | 740.512.2 | All electrical equipment requires a minimum degree of IP44 protection or placed in an enclosure having a rating of IP44. Regulation 740.512.2 (soi23.8, soi23.0) | C2 |
471 | 740.521.1 | Except for cables within an amusement device all cables require a minimum rated voltage of 450 / 750 volts. Regulation 740.521.1 (soi23.9, soi23.0) | C3 |
472 | 740.521.1 | Cables within an amusement device require a minimum voltage rating of 300 / 500 volts. Regulation 740.521.1 (soi23.9, soi23.0) | C3 |
473 | 740.521.1 | The routes of all cables buried in the ground require marking at suitable intervals. Regulation 740.521.1 (soi23.9, soi23.0) | C3 |
474 | 740.521.1 | Where there is a risk of damage due to external influences, armoured cables or cables protected against mechanical damage are required. Regulation 740.521.1 (soi23.9, soi23.0) | C2 |
475 | 740.521.1 | Mechanical protection for cables is required where they are used in public areas. Regulation 740.521.1 (soi23.9, soi23.0) | C2 |
476 | 740.521.1 | Mechanical protection for cables is required where wiring systems cross roads or walkways. Regulation 740.521.1 (soi23.9, soi23.0) | C2 |
477 | 740.521.1 | Wiring systems require to be of flexible construction where they are subject to movement. Regulation 740.521.1 (soi23.9, soi23.0) | C2 |
478 | 740.526 | Joints of electrical connections require being made in appropriate enclosure(s) having a degree of protection of at least IPXXD or IP4X. Regulation 740.526 (soi23.10, soi23.0) | C2 |
479 | 740.526 | Suitable cable anchorages are required where strain can be placed upon electrical terminals. Regulation 740.526 (soi23.10, soi23.0) | C2 |
480 | 740.537.2.1 | A readily accessible and identifiable means of isolation is required for every separate temporary electrical installation for a booth, stand or amusement device. The means of isolation requires selecting and erecting in accordance with Regulation 537.2. Regulation 740.537.2.1 (soi23.11, soi23.0) | C2 |
481 | 740.537.2.1.1 | A readily accessible and identifiable means of isolation is required for distribution circuit(s) supplying outdoor installation(s). The means of isolation requires selecting and erecting in accordance with Regulation 537.2. Regulation 740.537.2.1.1 (soi23.12, soi23.0) | C2 |
482 | 740.537.2.2 | Devices for isolation require to be able to disconnect all the live conductors (the neutral is a live conductor). Regulation 740.537.2.2 (soi23.13, soi23.0) | C3 |
483 | 740.55.1.1 | All luminaires and decorative lighting chains require a suitable IP rating and be installed so as not to impair it's ingress protection and is securely fixed to the structure or support and unless designed for the purpose, it's weight is not carried by the supply cable. Regulation 740.55.1.1 (soi23.14, soi23.0) | C2 |
484 | 740.55.1.1 | Luminaires and decorative lighting chains mounted below arm's reach (2.5metres) from floor level or otherwise accessible require adequate fixing and sited or guarded to prevent injury to persons or risk of fire by ignition of materials. Regulation 740.55.1.1 (soi23.15, soi23.0) | C2 |
485 | 740.55.1.1 | Luminaires and decorative lighting chains mounted below arm's reach (2.5metres) from the floor or otherwise accessible require having access to the fixed light source by the removal of a barrier or an enclosure by the use of a tool. Regulation 740.55.1.1 (soi23.15, soi23.0) | C2 |
486 | 740.55.1.2 | Non-compatible cable has been used where insulation piercing lampholders are fitted. Regulation 740.55.1.2 (soi23.16, soi23.0) | C2 |
487 | 740.55.1.2 | Where insulation piercing lampholders are being used they are required to be of the non-removable type once fitted. Regulation 740.55.1.2 (soi23.16, soi23.0) | C3 |
488 | 740.55.1.3 | All lamps in shooting galleries and other sideshows where projectiles are used require suitable protection. Regulation 740.55.1.3 (soi23.17, soi23.0) | C2 |
489 | 740.55.1.4 | Transportable floodlights require mounting so that the luminaire is inaccessible. Regulation 740.55.1.4 (soi23.18, soi23.0) | C2 |
490 | 740.55.1.4 | Transportable floodlights require a flexible supply cable type. Regulation 740.55.1.4 (soi23.18, soi23.0) | C2 |
491 | 740.55.1.4 | Supply cable(s) for transportable floodlights require protection against mechanical damage. Regulation 740.55.1.4 (soi23.18, soi23.0) | C2 |
492 | 740.55.1.5 | Luminaires and/or floodlights requires to be sited, fixed and protected against ignition of material caused by the danger of focusing or concentration of heat. Regulation 740.55.1.5 (soi23.19, soi23.0) | C2 |
493 | 740.55.3.1 | Electrical discharge lamp equipment incorporating signs, tubes or lamps on a booth, stand or amusement device with an operating voltage higher than 230/400 volts requires installing out of arm's reach or adequately protected against risk of injury to persons. Regulation 740.55.3.1 (soi23.20.1, soi23.0) | C2 |
494 | 740.55.3.2 | A separate circuit is required for the supply of signs, lamps or exhibits of electrical equipment incorporating discharge lamp installation(s) with an operating voltage higher than 230/400 volts. Regulation 740.55.3.2 (soi23.20.2, soi23.0) | C2 |
495 | 740.55.3.2 | A circuit supplying supply of signs, lamps or exhibits of electrical equipment incorporating discharge lamp installation(s) with an operating voltage higher than 230/400 volts requires controlling by an emergency switch which is easily identifiable and clearly labelled. Regulation 740.55.3.2 (soi23.20.2, soi23.0) | C2 |
496 | 740.55.5 | ELV transformer(s) and electronic converters require mounting out of arm's reach. Regulation 740.55.5 (soi23.21, soi23.0) | C2 |
497 | 740.55.5 | ELV transformer(s) and electronic converters require adequate ventilation. Regulation 740.55.5 (soi23.21, soi23.0) | C2 |
498 | 740.55.5 | ELV transformer(s) and electronic converters require a manual reset protective device (e.g. mcb) installed in the secondary circuit. Regulation 740.55.5 (soi23.21, soi23.0) | C2 |
499 | 740.55.7 | An adequate number of sockets has not been provided. Regulation 740.55.7 (soi23.22.1, soi23.0) | C3 |
500 | 740.55.7 | Socket-outlets dedicated to lighting circuits require to be placed out of arm's reach. Regulation 740.55.7 (soi23.22.2, soi23.0) | C2 |
501 | 740.55.7 | Socket-outlets dedicated to lighting circuits require marking according to their purpose. Regulation 740.55.7 (soi23.22.2, soi23.0) | C3 |
502 | 740.55.7 | Where socket-outlets, couplers and plugs are used outdoors they are required to be of the correct type (BS EN 60309-1 or BS EN 60309-2). Regulation 740.55.7 (soi23.22.3, soi23.0) | C2 |
503 | 740.55.8 | At every amusement device a connection point readily accessible and permanently marked indicating it's rated voltage, rated current and rated frequency is required. Regulation 740.55.8 (soi23.23, soi23.0) | C3 |
504 | 740.551.8 | Electric dodgems require operating at a maximum voltage of 50 V a.c or 120 V d.c. Regulation 740.551.8 (soi23.24.1, soi23.0) | C2 |
505 | 740.551.8 | Electric dodgems require having a circuit that is electrically separated from the supply mains by means of a transformer or a motor-generator set. Regulation 740.551.8 (soi23.24.1, soi23.0) | C2 |
506 | 740.551.8 | Electrical equipment associated with the generator fixing securely and where required mounted on anti-vibration mountings. Regulation 740.551.8 (soi23.24.2, soi23.0) | C2 |
507 | 740.551.8 | The requirements for the earthing arrangement in accordance with Regulation 542.1 where a TN, TT or IT system supplied by a generator and, where earth electrodes are used in accordance with Regulation 542.2 have not been met. Regulation 740.551.8 (soi23.24.3, soi23.0) | C2 |
508 | 740.551.8 | The neutral conductor(s) of the star-point of generator(s) require to be connected to the exposed-conductive-parts of the generator(s) – (not applicable for an IT system). Regulation 740.551.8 (soi23.24.4, soi23.0) | C2 |
509 | 753.411.3.2 | Heating systems require disconnecting device(s) by use of an RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn. Regulation 753.411.3.2 (soi24.1, soi24.0) | C2 |
510 | 753.415.1 | Circuit(s) supplying heating equipment of Class II construction or equivalent insulation require additional protection by use of an RCD(s) having a rated residual operating current (IΔn) not exceeding 30mA and an operating time not exceeding 40 ms at a residual current of 5 Iδn. Regulation 753.415.1 (soi24.1, soi24.0) | C2 |
511 | 753.514 | The relevant information as shown by Figure 753 for the user of the installation has not been supplied or is missing. Regulation 753.514 (soi24.2, soi24.0) | C3 |
512 | * | Where ceiling heating is installed, furniture is placed (cupboards, wardrobes etc. and anything stored on top) where it may cause over heating or damage to the heating element. Part of Figure 753 “Information for the user of the installation” (soi24.3, soi24.0) | C2 |